Daikin REYQ72PAYD Installation Manual

Browse online or download Installation Manual for Split-system air conditioners Daikin REYQ72PAYD. Daikin REYQ72PAYD Installation manual User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - INSTALLATION MANUAL

INSTALLATION MANUALSystem air conditionerEnglishFrançaisEspañolREYQ72PAYDREYQ96PAYDREYQ120PAYDREYQ72PATJREYQ96PATJREYQ120PATJ

Page 2

6 English6-5 Example of connectionB1 B2 B3 B4Example of connection(Connection of 8 indoor units)Outside unitside(3 pipes)Indoor unitside(2 pipes)Sucti

Page 3 - L1 L2 L3

English 7Outside unit multi connection piping kit andRefrigerant branch kit selectionPipe size selection• Refrigerant branch kits can only be used wit

Page 4

8 EnglishRequired Conditions Example Drawings1. It is necessay to increase the pipe size between the first branch kit and the final branch kit. (Reduc

Page 5 - 1. FIRST OF ALL

English 97. FIELD WIRINGNOTE• All field wiring and components must be installed by a licensed elec-trician and must comply with relevant local and nat

Page 6 - 1-2 Special notice of product

10 EnglishNOTE• Open the knock holes with a hammer or the like.• After knocking out the holes, we recommend you remove any burrs and paint them using

Page 7 - 3. SELECTION OF LOCATION

English 11• When two wires are connected to a single terminal, connect them so that the rear sides of the crimp contacts face each other. Also, make s

Page 8 - 6. REFRIGERANT PIPING

12 English<Vacuum drying>Evacuate the system from the liquid pipe, suction gas pipe, HP/LP gas pipe and equalizer pipe shutoff valve service por

Page 9 - English 5

English 13Tightening torqueThe sizes of the shutoff valves on each model and the tightening torque for each size are listed in the table below.<Siz

Page 10 - 6-5 Example of connection

14 EnglishCAUTION• Make sure to use the protect tool (protective groves and goggles) when charging the refrigerant.• Due to a danger of liquid hammer,

Page 11 - Pipe size selection

English 15• After H2P stop blinking (about 12 minutes after turning on the power), check H2P is OFF.If H2P is ON, check the malfunction code in the re

Page 12 - 8 English

figure 1 figure 3figure 2figure 4 figure 6figure 5figure 7 figure 8 figure 9 figure 10figure 11figure 1221≥3/8≥3/8≥3/8≥3/4≥3/4≥2≥2≥2≥7-7/8≥15-3/4 ≥15-

Page 13 - 7. FIELD WIRING

16 English6.After completing the additional refrigerant charging, record the charging amount on the accessory “REQUEST FOR THE INDICATON” label (Insta

Page 14 - 10 English

English 17• If the check operation was not performed at first istallation, the malfunc-tion code “U3” will be displayed in the remote controller. Perf

Page 15 - English 11

1645 Wallace Drive, Suite 110Carrollton, TX [email protected] EM09A062A(1002)FS

Page 16 - 9. PIPE INSULATION

figure 18figure 21figure 16 figure 17-2figure 19figure 20 figure 22figure 13 figure 14figure 17-1figure 15A34152B1212345611234347829651432123 TO IN/D

Page 17

figure 30figure 24figure 27 figure 29figure 31figure 25figure 23figure 26figure 283245 728Part A Part B Part C11910CAB16121314 14123456789101314151112

Page 18 - 14 English

English 1REYQ72PAYDREYQ96PAYDREYQ120PAYDRE YQ7 2PAT JRE YQ9 6PAT JREYQ120PATJVRVIII System air conditioner Installation manualCONTENTS1. FIRST OF ALL.

Page 19 - English 15

2 English• Make sure that all wiring is secured, that specified wires are used, and that no external forces act on the terminal connec-tions or wires.

Page 20 - 13. TEST RUN

English 3[DESIGN PRESSURE]Since design pressure is 478 psi, the wall thickness of pipes should be more carefully selected in accordance with the relev

Page 21 - English 17

4 English• If the height is exceeded the above, calculate h1 and h2 shown in the figure below, and add h2/2 to the service space of front side and h1/

Page 22 - 3P215731-8M EM09A062A

English 5• Outside unit multi connection piping kit and refrigerant branching kit (sold separately) are needed for connection of piping between out-si