Page view 23
Installation EDUS39-600-F7
23 FXLQ-M / FXNQ-M
NOTE
1. Allowable length of transmission wiring between indoor /
outdoor units and between the indoor unit and the remote
controller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft. (Total wiring length: 6560 ft.)
(2) Indoor unit – Remote controller:
Max. 1640 ft.
2. Insulated thickness: 1/16” or more.
9. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
9-1 HOW TO CONNECT WIRINGS
Remove the electric parts box lid and connect the wirings.
NOTE
For wiring to the electric parts box, see the WIRING DIA-
GRAM label on the back of the electric parts box lid.
Do not confuse remote controller wiring and transmission
wiring when connecting to the terminal block.
Fasten the wiring with accessory clamp (6).
If mounting a remote
controller on the unit,
wire as shown in the
figure on the right.
CAUTION
Never connect power supply wiring to the terminal block for
remote controller wiring as this could damage the entire
system.
Use only specified wire and connect wires to the terminal
tightly. Be careful wires do not place external stress on ter-
minals. Keep wires in neat order so as to not obstruct other
equipment. Make sure that the electric box lid fits tightly.
Incomplete connections could result in overheating and, in
worse case, result in electric shock or fire.
NOTE
To avoid a short circuit in the electric parts box, be sure to
apply sealing material or putty (not included) to the wiring
hole to prevent the infiltration of water as well as insects or
other small creatures. Otherwise a short-circuit may occur
inside the electric parts box.
When clamping the wirings, be sure no tension is applied to
the wire connections by using the included clamps. Also,
when wiring, make sure the electric parts box lid fits snugly
by arranging the wirings neatly and attaching the electric
parts box lid firmly. When attaching the electric parts box
lid, make sure no wirings get caught in the edges. Pass the
wirings through the hole to prevent damage.
FXLQ12 · 18 ·
24 MVJU
15A
Size must
comply with
local codes.
Sheathed
wire
(2 wire)
AWG
18-16
FXNQ12 · 18 ·
24 MVJU
USE COPPLE CONDUCTION
POWER SUPPLY
Electric parts box
Power supply wiring,
ground wiring
(Field wiring)
Remote controller wiring
(Field wiring)
Transmission wiring
(Field wiring)
REMOTE
CNTRL
FORCED
OFF
TRANSMISSION
WIRING
F1
P1
P2
F2
T1
T2
L1
L2
Clamp
fastener
Clamp (6)
(accessory)
Cut off excess
after tightening
Conduit
Lock nut
Pass through hole
of remote
controller
fastening plate.
Remote
controller wiring