Daikin FXHQ100MVE Service Manual Page 246

  • Download
  • Add to my manuals
  • Print
  • Page
    / 306
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 245
6L(1 7URXEOHVKRRWLQJ238QLILHG212))&RQWUROOHU
7URXEOHVKRRWLQJ 
NO
NO
NO
Cannot be used in
combination with a wiring
adapter for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and data
station cannot be used in
combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and parallel
interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Disconnect the schedule
timer's individual / combined
connector and reset the power
supply for all optional
controllers for centralized
control simultaneously.
Arrange so that the connector
for setting master control is
connected to one controller for
centralized control and reset
the power supply for all
optional controllers for
centralized control
simultaneously.
Disconnect the connector for
setting master control from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
YES
YES
Is the wiring adapter for
electrical appendices
connected?
YES
Is a schedule timer
connected?
Are there two or more
optional controllers for
centralized control
connected with the
connector for setting
master control?
YES
Is a parallel interface
connected?
NO
YES
Is the schedule timer's
individual/combined
connector connected?
YES
Is a data station
connected?
NO
NO
If the malfunction is still not cleared: