(8) Connect the piping. (See “5.REFRIGERANT PIPING WORK” and Fig. 10)
Seal the piping through-hole with putty corking material.
(9) Push on both bottom edges of the indoor unit using both hands and hook the tab on the back of
the indoor unit onto the installation panel (1). (Refer to Fig. 9)
At this time remove the buffering material placed in step (6).
Make sure power supply wiring, transmission wiring, ground wiring and remote controller wiring are not
caught inside the indoor unit.
When screwing in the indoor unit
Remove the front grill. (Refer to Fig. 7)
Secure the indoor unit to the installation panel (1) with the securing
screws (6). (Refer to Fig. 11)
5. REFRIGERANT PIPING WORK
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of the gas piping and the liquid piping.
Otherwise, a water leakage can result sometimes.
(When using a heat pump, the temperature of the gas piping can reach up to approximately 250°F, so use
insulation which is sufficiently resistant.)
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed
86°F or RH80 %, reinforce the refrigerant insulation. (13/16” or thicker) Condensation may form on the
surface of the insulating material.
Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not pos-
sible if the types of refrigerant are not the same.
DANGER
Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan, heater, stove or
cooking device. Exposure to this gas could result in severe injury or death.
Secure with
vinyl tape.
Seal with putty corking material.
Drain hose
Transmission wiring
and remote controller
wiring
Fig. 10
A
A arrow view
Refrigerant piping
Transmission wiring and
remote controller wiring
Wrap the insulating tape overlapping at least half the width with each wrap.
Wrap the insulating tape all the way to the L-shaped bend.
Refrigerant piping
Conduit
Installation panel
(accessory) (1)
Refrigerant piping
Insulating tape
(accessory) (4)
M4 × 12L
(accessory) (6)
Fig. 11
01_EN_3PN07521-1.fm Page 10 Monday, June 19, 2006 5:05 PM