Daikin FDXS25E7VMB User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 39
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Split - Sky Air
®
• Outdoor Unit
9
Outdoor Unit • Pair application • RXS-J
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables
FTXS20J2V1B + RXS20J2V1B
Cooling 50 Hz 220V-240V
AFR 9.4
BF 0.14
Indoor Outdoor temperature: (°CDB)
EWB EDB
20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.05 1.84 0.35 1.96 1.80 0.38 1.86 1.76 0.41 1.83 1.74 0.43 1.77 1.71 0.45 1.68 1.67 0.48
16.0 22 2.14 1.81 0.35 2.05 1.77 0.38 1.95 1.73 0.41 1.92 1.72 0.43 1.86 1.69 0.45 1.77 1.66 0.48
18.0 25 2.23 1.94 0.35 2.14 1.90 0.38 2.05 1.87 0.42 2.01 1.85 0.43
1.95 1.83 0.45
1.86 1.80 0.48
19.0 27 2.28 2.09 0.35 2.19 2.05 0.38 2.09 2.02 0.42 2.06 2.00 0.43
2.00 1.98 0.45
1.91 1.95 0.48
22.0 30 2.42 2.03 0.35 2.32 2.00 0.39 2.23 1.97 0.42 2.19 1.96 0.43 2.14 1.94 0.45 2.05 1.91 0.49
24.0 32 2.51 1.99 0.36 2.42 1.96 0.39 2.32 1.93 0.42 2.29 1.92 0.44 2.23 1.91 0.45 2.14 1.88 0.49
Heating 50 Hz 220V-240V
AFR 9.9
Indoor Outdoor temperature: (°CWB)
EDB
-10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI
15.0 1.82 0.52 2.12 0.54 2.43 0.57
2.79 0.60
3.04 0.62
20.0 1.72 0.53 2.03 0.55 2.33 0.58
2.70 0.61
2.94 0.63
22.0 1.69 0.54 1.99 0.56 2.30 0.59 2.66 0.62 2.91 0.64
24.0 1.65 0.54 1.95 0.57 2.26 0.59 2.63 0.62 2.87 0.64
25.0 1.63 0.54 1.94 0.57 2.24 0.59 2.61 0.62 2.85 0.64
27.0 1.59 0.55 1.90 0.57 2.20 0.60 2.57 0.63 2.81 0.65
Symbols
AFR: Air fl ow rate (m
3
/min.)
BF: Bypass factor
EWB: Entering wet bulb temp. (°C)
EDB: Entering dry bulb temp. (°C)
TC: Total capacity (kW)
SHC: Sensible heat capacity (kW)
PI: Power input (kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2.
shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping lenght: 5m
Level difference: 0m
6. Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D070643