4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables
FLXS35BAVMB + RXS35J2V1B
Cooling 50 Hz 220V-240V
AFR 8.6
BF 0.35
Indoor Outdoor temperature: (°CDB)
EWB EDB
20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.72 1.92 0.87 2.72 1.92 0.95 2.72 1.92 1.03 2.72 1.92 1.07 2.72 1.92 1.12 2.72 1.92 1.20
16.0 22 3.34 2.14 0.87 3.34 2.14 0.96 3.34 2.14 1.04 3.34 2.14 1.07 3.26 2.10 1.12 3.10 2.01 1.21
18.0 25 3.91 2.42 0.88 3.75 2.34 0.96 3.58 2.26 1.04 3.52 2.22 1.08
3.42 2.17 1.13
3.26 2.09 1.21
19.0 27 3.99 2.51 0.88 3.83 2.43 0.96 3.66 2.34 1.05 3.60 2.31 1.08
3.50 2.27 1.13
3.34 2.19 1.21
22.0 30 4.23 2.40 0.89 4.07 2.33 0.97 3.90 2.26 1.05 3.84 2.23 1.09 3.74 2.19 1.14 3.58 2.12 1.22
24.0 32 4.39 2.32 0.89 4.23 2.26 0.98 4.07 2.19 1.06 4.00 2.16 1.09 3.90 2.13 1.14 3.74 2.06 1.23
Heating 50 Hz 220V-240V
AFR 9.8
Indoor Outdoor temperature: (°CWB)
EDB
-10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI
15.0 2.69 1.04 3.14 1.09 3.60 1.14
4.14 1.20
4.50 1.24
20.0 2.55 1.07 3.01 1.12 3.46 1.17
4.00 1.23
4.36 1.27
22.0 2.50 1.08 2.95 1.13 3.40 1.18 3.94 1.24 4.31 1.28
24.0 2.44 1.09 2.90 1.14 3.35 1.19 3.89 1.25 4.25 1.29
25.0 2.42 1.10 2.87 1.15 3.32 1.20 3.86 1.26 4.18 1.30
27.0 2.36 1.11 2.81 1.16 3.26 1.21 3.81 1.27 3.91 1.30
Symbols
AFR: Air fl ow rate (m
3
/min.)
BF: Bypass factor
EWB: Entering wet bulb temp. (°C)
EDB: Entering dry bulb temp. (°C)
TC: Total capacity (kW)
SHC: Sensible heat capacity (kW)
PI: Power input (kW)
NOTES
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping lenght: 5m
(2) Level difference: 0m
2.
shows nominal (rated) capacities and power input.