Daikin BRC1E72 Setup Guide Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
Page 17 of 36 / OM 1169-1
Setup Guide
Enabling Setback Temperature Control
Unit On = Occupied period = Comfort Control
Indoor unit maintains the room temperature at the set-
point in the cooling/heating mode
Comfort setpoint range is congurable in each cooling
and heating mode on the remote controller
Unit Off = Unoccupied period = Setback Control
Enable Setback
Setback function is disabled (1e-2-01) by default
To enable it, set 1e-2-04
Field setting is available in the Service Settings
Refer to “Field Settings” on page 13 for step-by step
instructions.
Activating Filter Change Indicator
Refer to “Field Settings” on page 13 for step-by step
instructions.
Table 15: “Time to change filter” message; enable/disable
Code “Time to change lter” message
20-3-01 Enabled by default
20-3-02 Disabled
Table 16: “Time to change filter” message settings
Code “Time to change lter” message
20-0-2 and 20-1-1 Displays after 1250 hours
20-0-1 and 20-1-1 Displays after 2500 hours
20-0-2 and 20-1-2 Displays after 5000 hours
20-0-1 and 20-1-2 Displays after 10,000 hours
Limiting Setpoint Ranges
User can change the setpoint within the range
Setup setpoint is congurable between Cool setpoint max
+ 2°F (1°C) and 95°F
Setback setpoint is congurable between Heat setpoint
min – 2°F ( 1°C) and 40°F
Step 1.
Press and hold the “Cancel” button for 4 seconds or longer, to
enter “Service Settings” menu screen.
Press and hold the “Cancel”
button for 4 seconds.
Setting
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
1/3
Setting
Energy Saving Options
Setpoint Range Limitation
Setback Configuration
Step 2.
Select the temperature item with ◄► buttons. Change the
temperature with ▼▲ buttons.
Holding down the orbutton causes the number to
change continuously.
Setting
Setpoint Range Limitation
Cool
70
F
80
F
Heat
64
F
74
F
Setting
Energy Saving Options
Setpoint Range Limitation
Setback Configuration
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 35 36

Comments to this Manuals

No comments