SUBMITTAL DATED: December 23, 2013
Daikin Applied Georgia
1765 West Oak Parkway, Ste. 500
Marietta, GA 30062
Michael M Eckert, LEED AP; Sales Engineer
Cell: 678.372.5034
Michael.eckert@daikinapplied.com
PROJECT
Georgia State University
Project No 093-073-11
J – 183 Humanities – Law Building
85 Park Place
Atlanta, GA 30303
MECHANICAL CONTRACTOR
Gainesville Mechanical, Inc
2519 Monroe Dr
Gainesville, GA 30507
770.532.9130
MECHANICAL ENGINEER
Stevens & Wilkinson
100 Peachtree Street NW.
Suite 2500
Atlanta, GA 30303
Equipment
Daikin VRV Heat Pump Systems
Outdoor Unit TAGS: (HP-01~07)
1
Page view 0
1 2 3 4 5 6 ... 110 111

Summary of Contents

Page 1 - Equipment

SUBMITTAL DATED: December 23, 2013Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell

Page 2

11020.00 / J-183 GSU Humanities-Law 23 8129 - 7 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM7. Power Failure Mode: Automatically restart operati

Page 3

EDUS391005-R1 Capacity Tables (Reference Data)RXYQ-PBYD Heat Pump (460V) 39RXYQ96PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan m

Page 4

Capacity Tables (Reference Data) EDUS391005-R140 RXYQ-PBYD Heat Pump (460V)RXYQ120PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan

Page 5

EDUS391005-R1 Capacity Tables (Reference Data)RXYQ-PBYD Heat Pump (460V) 41RXYQ144PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan

Page 6

REFNET Pipe System EDUS391004-N14 Installation of Outdoor Units4. REFNET Pipe System4.1 REFNET Joint (Branch Kit)RXYQ72~360PBYD (460V)RXYQ72~360PBTJ (

Page 7

REFNET Pipe System EDUS391004-N22 Installation of Outdoor Units4.3 Outdoor Unit Multi Connection Piping KitRXYQ144~240PBYD (460V)RXYQ168~240PBTJ (208/

Page 8

EDUS391004-N REFNET Pipe SystemInstallation of Outdoor Units 231P218719105

Page 9

REFNET Pipe System EDUS391004-N24 Installation of Outdoor Units1P218720106

Page 10

EDUS391004-N REFNET Pipe SystemInstallation of Outdoor Units 251P218720107

Page 11

Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell: 678.372.5034Michael.eckert@daiki

Page 12

Submittal Data: DMS502B71 BACnet® Interface Job Name: Location:Purchaser: Engineer:Submitted To: For: Reference Approval Construction Subm

Page 13

11020.00 / J-183 GSU Humanities-Law 23 8129 - 8 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM7. The inverter driven comprassor in each condensing

Page 14

Daikin air conditioner monitoring and control points accessible through the DMS502B71Check the appropriate box indicating the required integrated poin

Page 15 - VRV SPECIFICATIONS

GSU Humanities - Law BuildingAtlanta, GA    Stevens & Wilkinson   12.23.13

Page 16

11020.00 / J-183 GSU Humanities-Law 23 8129 - 9 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM6. Condensate Drainage: Built-in condensate drain pa

Page 17

11020.00 / J-183 GSU Humanities-Law 23 8129 - 10 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEMF. Wall Surface-Mounted Units: Finished white casin

Page 18

11020.00 / J-183 GSU Humanities-Law 23 8129 - 11 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEMB. Prepare and start equipment and system in accorda

Page 19

Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell: 678.372.5034Michael.eckert@daiki

Page 20

Section 238129Daikin AC Model Number:RXYQ72PBYDRXYQ96PBYDRXYQ120PBYDRXYQ144PBYD (2x RXYQ72PBYD) Part 1 – GENERALVARIABLE REFRIGERANT VOLUME (VRVIII

Page 21

1.02 VRVIII FEATURES AND BENEFITSA. Voltage Platform – Heat pump condensing units will be available with a 460V/3/60 power supply.B. Advanced Zoning

Page 22

O. Low Sound Levels – Each system will use indoor and condensing units with quiet operation as low as 27 dB(A).1.03 QUALITY ASSURANCEA. The units wil

Page 23 - RXYQ120PBYD 21 25 5.4 + 8.4

The mechanical contractor’s installation price will be based on the systems installation requirements. The mechanical contractor bids with complete

Page 24

Submittal Coordination Comments:1. Contractor to verify electrical information and communication protocol before release. (BACnet interface is curren

Page 25 - (Indoor 47°F DB / 43°F WB

The operating range in heating will be 0°F DB – 77°F DB / -4°F WB – 60°F WB.Cooling mode indoor room temperature range will be 57°F-77°F WB. Heating

Page 26

fan motors, over current protection for the inverter and anti-recycling timers.10. To ensure the liquid refrigerant does not flash when supplying to

Page 27

7. Night setback control of the fan motor for low noise operation by way of automatically limiting the maximum speed will be a standard feature. Oper

Page 28

a minimum of 6 compressors. In the event of compressor failure the remaining compressors will continue to operate and provide heating or cooling as

Page 29 - VRV SYSTEM DETAILS

FXFQ INDOOR UNIT – ROUND FLOW CEILING CASSETTE UNIT (3’x3’)FXZQ INDOOR UNIT – 4 WAY CEILING CASSETTE UNIT (2’x2’)FXMQ_M INDOOR UNIT – CONCEALED CEILI

Page 30 - 1. Material List

temperature when used with Daikin remote control BRC1E72 and BRC2A71. The indoor units sound pressure will range from 27 dB(A) to 34 dB(A) at low sp

Page 31 - 2. Indoor Unit Details

6. The cabinet will be constructed with sound absorbing foamed polystyrene and polyethylene insulation.7. Optional high efficiency MERV 13 air filter

Page 32 - 2.2. HP-01 - RXYQ144PBYD

A. General: Daikin indoor unit FXAQ will be a wall mounted fan coil unit, operable with refrigerant R-410A, equipped with an electronic expansion va

Page 33 - 2.3. HP-02 - RXYQ96PBYD

4. Return air will be through a resin net mold resistant filter.5. The indoor units will be equipped with a condensate pan.6. The indoor units will b

Page 34 - 2.4. HP-03 - RXYQ120PBYD

Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell: 678.372.5034Michael.eckert@daiki

Page 35 - 2.5. HP-04 - RXYQ144PBYD

Table of Contents – GSU Humanities Law Bldg6SHFLILFDWLRQ&'(        9596SHFLILFDWLRQV959

Page 36 - 2.6. HP-05 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 37 - 2.7. HP-06 - RXYQ72PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 38 - 2.8. HP-07 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 39 - 3. Outdoor Unit Details

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 40 - 3.2.Outdoor Details

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 41 - 3.2.1. HP-01 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 42 - 3.2.2. HP-02 - RXYQ96PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 43 - 3.2.3. HP-03 - RXYQ120PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 44 - 3.2.4. HP-04 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 45 - 3.2.5. HP-05 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 46 - 3.2.6. HP-06 - RXYQ72PBYD

SECTION 23 8129VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEMREVISION #6PART 1 GENERAL1.01 SECTION INCLUDESA. Variable refrigerant volume HVAC system

Page 47 - 3.2.7. HP-07 - RXYQ144PBYD

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 48 - 4. Piping Diagrams

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 49 - 4.2.Piping HP-02

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 50 - 4.3.Piping HP-03

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 51 - 4.4.Piping HP-04

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 52 - 4.5.Piping HP-05

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 53 - 4.6.Piping HP-06

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 54 - 4.7.Piping HP-07

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 55 - 5. Wiring Diagrams

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 56 - 5.2. Wiring HP-02

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 57 - 5.3. Wiring HP-03

11020.00 / J-183 GSU Humanities-Law 23 8129 - 2 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEMg. Air Flow: Cubic feet per minute (Cubic meters per

Page 58 - 5.4. Wiring HP-04

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 59 - 5.5. Wiring HP-05

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 60 - 5.6. Wiring HP-06

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 61 - 5.7. Wiring HP-07

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 62 - 6. Centralized Controllers

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 63 - 6.2.Control group 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 64 - 6.3. Dimensional Drawings

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 65 - INDOOR UNIT DETAILS

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 66 - 1. Specifications

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 67 - Wall Mounted Type

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 68 - 2. Dimensions

11020.00 / J-183 GSU Humanities-Law 23 8129 - 3 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM3. Identification of replaceable parts and local sour

Page 69 - 3D075390A

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 70 - 4. Wiring Diagrams

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 71 - 6. Safety Devices Setting

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 72 - 7. Capacity Tables

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 73 - 7.2 Heating Capacity

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome

Page 74

Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell: 678.372.5034Michael.eckert@daiki

Page 75 - FXFQ-P 3

Specifications EDUS391100-F62 FXAQ-PVJU1. SpecificationsWall Mounted TypeNotes:+ 1 Nominal cooling capacities are based on the following conditions: R

Page 76

EDUS391100-F6 SpecificationsFXAQ-PVJU 3Wall Mounted TypeNotes:+ 1 Nominal cooling capacities are based on the following conditions: Return air tempera

Page 77 - FXFQ48PVJU

Dimensions EDUS391100-F64 FXAQ-PVJU2. DimensionsFXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJUUnit (in.)3D075388A68

Page 78

Dimensions EDUS391100-F66 FXAQ-PVJUFXAQ24PVJUUnit (in.)3D075390A69

Page 79

11020.00 / J-183 GSU Humanities-Law 23 8129 - 4 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM3. Substitution requests will be considered only if r

Page 80 - 6. Capacity Tables

Wiring Diagrams EDUS391100-F68 FXAQ-PVJU4. Wiring DiagramsFXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJU/FXAQ18PVJU/FXAQ24PVJU3D07535470

Page 81 - 6.2 Heating Capacity

EDUS391100-F6 Electric CharacteristicsFXAQ-PVJU 95. Electric Characteristics6. Safety Devices Setting4D075550C: 4D047085CFXAQ - PVJU71

Page 82 - OUTDOOR UNIT DETAILS

Capacity Tables EDUS391100-F610 FXAQ-PVJU7. Capacity Tables7.1 Cooling CapacityFXAQ-P [Cooling capacity]TC: Total capacity: MBhSHC: Sensible heat ca

Page 83

EDUS391100-F6 Capacity TablesFXAQ-PVJU 117.2 Heating CapacityFXAQ-P [Heating capacity]TC: Total capacity: MBhRefer to outdoor unit capacity tables for

Page 84 - RXYQ-PBYD Heat Pump (460V) 3

Specifications EDUS391000-F12 FXFQ-P1. SpecificationsCeiling Mounted Cassette Type (Round Flow) Notes:+ 1 Nominal cooling capacities are based on the

Page 85

EDUS391000-F1 SpecificationsFXFQ-P 3Ceiling Mounted Cassette Type (Round Flow)Notes:+ 1 Nominal cooling capacities are based on the following conditio

Page 86 - 8 RXYQ-PBYD Heat Pump (460V)

Dimensions EDUS391000-F14 FXFQ-P2. DimensionsFXFQ09PVJUFXFQ12PVJUFXFQ18PVJUUnit (in.)3D070522DO NOT PLACE THE UNIT IN AREAS WITH EXCESSIVE HUMIDITY.W

Page 87 - RXYQ-PBYD Heat Pump (460V) 9

Dimensions EDUS391000-F16 FXFQ-PFXFQ36PVJUFXFQ48PVJUUnit (in.)3D070523DO NOT PLACE THE UNIT IN AREAS WITH EXCESSIVE HUMIDITY.WHEN HUMIDITY EXCEEDS 80

Page 88 - 3. Service Space

Wiring Diagrams EDUS391000-F18 FXFQ-P4. Wiring DiagramsFXFQ09PVJU / FXFQ12PVJU / FXFQ18PVJU / FXFQ24PVJU / FXFQ30PVJU / FXFQ36PVJU / FXFQ48PVJU3D07030

Page 89

EDUS391000-F1 Electric CharacteristicsFXFQ-P 95. Electric Characteristics4D070525A79

Page 90 - 18 RXYQ-PBYD Heat Pump (460V)

11020.00 / J-183 GSU Humanities-Law 23 8129 - 5 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM1. Minimum Piping Length from Outdoor/Central Unit(s)

Page 91 - 6. Field Wiring

Capacity Tables EDUS391000-F110 FXFQ-P6. Capacity Tables6.1 Cooling CapacityFXFQ-P [Cooling Capacity]TC : Total capacity ; MBhSHC : Sensible heat capa

Page 92 - 20 RXYQ-PBYD Heat Pump (460V)

EDUS391000-F1 Capacity TablesFXFQ-P 116.2 Heating CapacityFXFQ-P [Heating Capacity]TC :Total capacity ; MBhIndoor UnitOutdoor Air Temp.Indoor Air Temp

Page 93 - 7. Electric Characteristics

Daikin Applied Georgia1765 West Oak Parkway, Ste. 500Marietta, GA 30062Michael M Eckert, LEED AP; Sales EngineerCell: 678.372.5034Michael.eckert@daiki

Page 94 - RXYQ-PBYD Heat Pump (460V) 23

Specifications EDUS391005-R12 RXYQ-PBYD Heat Pump (460V)1. SpecificationsNotes:+1 Indoor temp. : 80°FDB (27°CDB), 67°FWB(19.4°CWB) / outdoor temp. : 9

Page 95 - RXYQ72PBYD

EDUS391005-R1 SpecificationsRXYQ-PBYD Heat Pump (460V) 3Notes:+1 Indoor temp. : 80°FDB(27°CDB), 67°FWB(19.4°CWB) / outdoor temp. : 95°FDB (35°CDB) / E

Page 96

EDUS391005-R1 DimensionsRXYQ-PBYD Heat Pump (460V) 72. DimensionsRXYQ72PBYD3D07051785

Page 97

Dimensions EDUS391005-R18 RXYQ-PBYD Heat Pump (460V)RXYQ96PBYD / RXYQ120PBYDC: 3D070518A86

Page 98

EDUS391005-R1 DimensionsRXYQ-PBYD Heat Pump (460V) 9RXYQ144PBYDC: 3D070788from Section 3. NOTE: If more units are to be installed than are shown in Se

Page 99

Service Space EDUS391005-R114 RXYQ-PBYD Heat Pump (460V)3. Service SpaceRXYQ72PBYD / RXYQ96PBYD / RXYQ120PBYD / RXYQ144PBYD / RXYQ168PBYD / RXYQ192PBY

Page 100 - RXYQ96PBYD

EDUS391005-R1 Wiring DiagramsRXYQ-PBYD Heat Pump (460V) 175. Wiring DiagramsRXYQ72PBYD3D070562CGROUNDGROUND89

Page 101 - RXYQ120PBYD

11020.00 / J-183 GSU Humanities-Law 23 8129 - 6 VARIABLE REFRIGERANT VOLUME (VRV)HVAC SYSTEM7. Energy Efficiency: Report EER, IEER and COP based

Page 102 - RXYQ144PBYD

Wiring Diagrams EDUS391005-R118 RXYQ-PBYD Heat Pump (460V)RXYQ96PBYD / RXYQ120PBYD3D070563CGROUNDGROUND90

Page 103 - 4. REFNET Pipe System

EDUS391005-R1 Field WiringRXYQ-PBYD Heat Pump (460V) 196. Field WiringRXYQ72PBYD / RXYQ96PBYD / RXYQ120PBYDC: 3D058621Dground4) Field wiring diagram i

Page 104 - RXYQ168~240PBTJ (208/230V)

Field Wiring EDUS391005-R120 RXYQ-PBYD Heat Pump (460V)RXYQ144PBYD / RXYQ168PBYD / RXYQ192PBYD / RXYQ216PBYD / RXYQ240PBYDC: 3D059672DgroundBe sure to

Page 105 - 1P218719

Electric Characteristics EDUS391005-R122 RXYQ-PBYD Heat Pump (460V)7. Electric Characteristics3D067246MOP :Maximum Overcurrent Protection (A)MOP MOP

Page 106 - 1P218720

EDUS391005-R1 Electric CharacteristicsRXYQ-PBYD Heat Pump (460V) 23C: 3D067250B MCA MOP20.2 + 20.2 25 + 25 20.3 + 20.3

Page 107

EDUS391005-R1 Capacity Tables (Reference Data)RXYQ-PBYD Heat Pump (460V) 258. Capacity Tables (Reference Data)8.1 Cooling Capacity (RXYQ-PBYD)These ta

Page 108 - ACCESSORIES

Capacity Tables (Reference Data) EDUS391005-R126 RXYQ-PBYD Heat Pump (460V)RXYQ96PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan m

Page 109 - Submittal Data: DMS502B71

EDUS391005-R1 Capacity Tables (Reference Data)RXYQ-PBYD Heat Pump (460V) 27RXYQ120PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan

Page 110

Capacity Tables (Reference Data) EDUS391005-R128 RXYQ-PBYD Heat Pump (460V)RXYQ144PBYDTC: Total capacity ; MBHPI: Power Input ; kW (Comp.+Outdoor fan

Page 111 - Submittal Data Sheet

Capacity Tables (Reference Data) EDUS391005-R138 RXYQ-PBYD Heat Pump (460V)8.2 Heating Capacity (RXYQ-PBYD)RXYQ72PBYDTC: Total capacity ; MBHPI: Power