Daikin FHQ125CAVEB Installation Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
11 English
For the tightening torque, refer to the Table 1.
Table 1
CAUTION
Do not have oil adhere to the screw fixing part of resin parts.
If oil adheres, it may weaken the strength of screwed part.
Do not tighten flare nuts too tight.
If a flare nut cracks, the refrigerant may leak.
If there is no torque wrench, use Table 2 as a rule of thumb. When tightening a flare nut with a spanner
harder and harder, there is a point where the tightening torque suddenly increases. From that position,
tighten the nut additionally the angle shown in Table 2. After the work is finished, check securely that there
is no gas leak. If the nut is not tightened as instructed, it may cause slow refrigerant leak and result in mal-
function (such as does not cool or heat).
Table 2
CAUTION
Insulation of field piping must be carried out up to the connection inside the casing. If the piping is
exposed to the atmosphere, it may cause sweating or burn due to touching the piping, electric shocks or
a fire due to the wiring touching the piping.
Piping size (mm) Tightening torque (N·m)
Dimension for processing
flare A (mm)
Flare shape
φ 6.4 15.7 ± 1.5 8.9 ± 0.2
φ 9.5 36.3 ± 3.6 13.0 ± 0.2
φ 12.7 54.9 ± 5.4 16.4 ± 0.2
φ 15.9 68.6 ± 6.8 19.5 ± 0.2
Piping size (mm) Tightening angle Recommended arm length of tool used
φ 6.4 60° – 90° Approximately 150mm
φ 9.5 60° – 90° Approximately 200mm
φ 12.7 30° – 60° Approximately 250mm
φ 15.9 30° – 60° Approximately 300mm
R0.4-0.8
90˚±2˚
A
45˚±2˚
01_EN_3P249378-6L.fm Page 11 Sunday, September 30, 2012 2:30 PM