Daikin AKZJ8Series Specifications Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
14
Before
Operation
Handling
50
40
45
30
20
10
51020304050
5
Room temperature
Tank liquid temperature (˚C)
(˚C)
Allowable operating range
Electric wiring
2
• Check if the unit mounting parts are securely fastened to the tank top plate with bolts.
• Check for any obstacle that blocks air intake or exhaust flow.
(Do not put an obstacle within 500 mm from the air intake/exhaust port.)
Applicable liquid
5
Liquid level in the tank
Delay timer
3
Be sure to maintain the liquid level in the tank within the specified range. (See page .)
(Operating the unit with a liquid level out of the specified range causes a fault of the unit.)
• The OILCON unit incorporates a delay timer. Therefore, when the compressor is stopped once and then restarted, the
compressor may not start. This does not mean a fault of the unit.
(See page .)
4
The OILCON unit can be used for water-soluble cutting/grinding fluid, cutting/grinding oil, water for industrial use, lubricating
oil, hydraulic oil (mineral oil). It cannot be applied to the following oils (liquids), and a liquid that may corrode the cooling coil
(SUS304).
1) Flame-resistant hydraulic oil Phosphoric ester type
Chlorinated hydrocarbon type
Water + glycol type
W/O, O/W emulsion type
2) Chemicals and food liquids (drinking water etc.)
3) Fuels (kerosene, gasoline, etc.)
4) Water other than for industrial use
6
Before operating the Oil Cooling Unit,
be sure to read through this instruction
manual and understand the contents of
this manual.
CAUTION
Before Operation
Before operating the Oil Cooling Unit, check the following items:
Operating environment
1
• Check the atmosphere for any factor (dust, oil mist, high temperature, high humidity, etc.) that may adversely affect the unit.
Check if the unit is not installed in explosive atmosphere (that may cause evolution, inflow, retention or leak of inflammable gas).
• The operating range is limited. Make sure that the operating conditions are within the following range.
(Note: If this unit is operated out of the specified range, the protection devices may be activated, or the service life may be shortened.)
5
18
Electric wiring
Check if the cable size is larger than the specified size. (Refer to Wiring procedure on page .)
Check if the ground cable is securely connected.
Be sure to use a commercial power supply. Using an inverter power supply may result in burnout.
Check if the power supply voltage is within the following range:
50 Hz...........200 V ±10%
60 Hz...........200/220 V ±10%
Check if a circuit breaker is provided exclusively for each Oil Cooling Unit.
8
PIM00132A_EN.fm 14 ページ 2007年9月20日 木曜日 午後3時4分