VRV FOR AIR HANDLING APPLICATIONS
VRV for air handling application
A R-410A inverter condensing units range for multi application ›
with air handling units.
Inverter controlled units ›
Large capacity range (from 5 to 18HP) ›
Cooling only ›
R-410A ›
Control z: ›
control of air temperature (suction temperature, room
temperature) via Daikin control (no DDC controller needed)
Large range of expansion valve kits available ›
BRC1D52 is used to set the set point temperature (connected ›
to the EKEXMCB).
scroll
gas pipe
liquid pipe
F1, F2 communication
EXV-kit
Air handling unit
(Field Supply)
Combination table
Outdoor unit
Control box
Expansion valve kit
control z
class 50 class 63 class 80 class 100 class 125 class 140 class 200 class 250
EKEXMCB EKEXV50 EKEXV63 EKEXV80 EKEXv100 EKEXV125 EKEXV140 EKEXV200
EKEXV250
3ph
RXQ5P
xxxxxxxxx
RXQ8P
xxxxxxxxx
RXQ10P
xxxxxxxxx
RXQ12P
xxxxxxxxx
RXQ14PA
xxxxxxxxx
RXQ16PA
xxxxxxxxx
RXQ18PA
xxxxxxxxx
Cooling only
RXQ-P(A)
5 8 10 12 14 16
18
Capacity range HP
5 8 10 12 14 16
18
Capacity Cooling kw
14.0 22.4 28.0 33.5 40.0 45.0 49.0
Power input (Nominal) Cooling kw
3.52 5.56 7.42 9.62 12.4 14.2 16.2
Dimensions (Height x Width x Depth) mm
1,680x635x765 1,680x930x765 1,680x1,240x765
Weight kg
157 185 238 315 323
Sound Level
Sound Power Cooling dBA
72 78 80 83
Sound Pressure Cooling dBA
54 57 58 60
63
Air Flow Rate (nominal at 230V)
Cooling
m³/min
95 171 185 196 233 239
Operation Range Cooling Min~Max °CDB
-5.0~43.0
Refrigerant
R-410A
Power Supply
3N~/400V/50Hz
Max n° of indoor units to be connected
8 131619232629
Piping connections Liquid (OD)/Gas mm
9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 22.2 12.7 / 28.6 15.9 / 28.6
96