Daikin VAM-GVJU Specifications Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
150 250 350 500 650 800 1000 1500 2000
74 72 75 74 74 74 75 75 75
74 72 75 74 74 74 75 75 75
79 77 80 77 77 76 76.5 78 78
64 64 65 62 63 65 66 66 66
64 64 65 62 63 65 66 66 66
69 68 70 67 66 67 68 68 70
58 58 61 58 58 60 61 61 61
58 58 61 58 58 60 61 61 61
64 62 67 63 63 62 63 64 66
1 ~, 220~240V, 50Hz
27-28.5 28-29 32-34 33-34.5 34.5-35.5 36-37 36-37 39.5-41.5 40-42.5
26-27.5 26-27 31.5-33 31.5-33 33-34 34.5-36 35-36 38-39 38-41
20.5-21.5 21-22 23.5-26 24.5-26.5 27-28 31-32 31-32 34-36 35-37
27-28.5 28-29 32-34 33.5-34.5 34.5-35.5 36-37 36-37 40.5-41.5 40-42.5
26.5-27.5 27-28 31-32.5 32.5-33.5 34-35 34.5-36 35.5-36 38-39 38-41
20.5-21.5 21-22 24.5-26.5 25.5-27.5 27-28.5 31-33 31-32 33.5-36 35-37
galvanised steel plate
self-extinguishable urethane foam
269 x 760 x 509 285 x 812 x 800 348 x 988 x 852 348x988x1,140 710x1,498x852 710x1,498x1,140
24 33 48 61 132 158
air to air cross flow total heat (sensible heat + latent heat) exchange
specially processed non-flammable paper
multidirectional fibrous fleeces
sirroco fan
150 250 350 500 650 800 1,000 1,500 2,000
150 250 350 500 650 800 1,000 1,500 2,000
110 155 230 350 500 670 870 1,200 1,400
69 64 98 98 93 137 157 137 137
39 39 70 54 39 98 98 98 78
20 20 25 25 25 49 78 49 59
0.030 x 2 0.090 x 2 0.140 x 2 0.230 x 2 0.230 x 4
Ø 100 Ø 150 Ø 200 Ø 250 Ø 350
-1C ~ +5CDB, 80% RH or less
p. 18
VI. Specifications
VAM-FA
VAM-FA
Temperature exchange efficiency (%) ultra-high
high
low
Enthalpy exchange efficiency (%) for heating ultra-high
high
low
for cooling ultra-high
high
low
Power Supply VE
Sound pressure level dB(A) Heat exchange mode ultra-high
high
low
Bypass mode ultra-high
high
low
Casing
Insulation Material
Dimensions HxWxD mm
Weight kg
Heat Exchange System
Heat Exchange Element Material
Air Filter
Fan Type
Air Flow Rate (m
3
/h) ultra-high
high
low
External static pressure (Pa) ultra-high
high
low
Motor Output kW
Connection Duct Diameter mm
Unit ambient condition
Notes: Air flow rate can be changed over to low mode or high mode.
Sound pressure level is measured at 1.5m below the center of the body.
Sound pressure level is measured in an anechoic chamber.
Sound pressure levels generally become higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound pressure level at the air discharge port is about 8dB higher than the unit's sound level.
Even when the outdoor temperature is below -1C, the system is operable down to -20°C with the preheater installed at the outdoor air intake side.
specifications
V AM800FA
Ventilation
hayez_EPCE05-44B 8/02/06 13:32 Page 18
mov93585_EPCE05-44B
Cyan Magenta Yellow Black
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 24

Comments to this Manuals

No comments