System air conditionerINSTALLATION MANUALREYQ8PY1BREYQ10PY1BREYQ12PY1BREYQ14PY1BREYQ16PY1BEnglishDeutschFrançaisEspañolItalianoΕλληνικÜNederlandsPortu
English 44.The refrigerant R410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed th
5 English6-3 Pipe connection• Be sure to perform nitrogen permutation or nitrogen blow when brazing. (Refer to figure 8)Brazing without performing nit
English 66-5 Example of connectionExample of connection(Connection of 8 indoor units)IndoorunitsideOutdoorunitside12BSUnitSuction gas pipeHP/LP gas pi
7 EnglishOutdoor unit multi connection piping kit andRefrigerant branch kit selectionPipe size selection• Refrigerant branch kits can only be used wit
English 8Required Conditions Example Drawings1. It is necessary to increase the pipe size between the first branch kit and the final branch kit. (Redu
9 English7. FIELD WIRINGCaution• All field wiring and components must be installed by a licensed electrician and must comply with relevant local and n
English 107-4 Transmission Wiring Connection Procedure• Referring to figure 19 connect the transmission wiring between outdoor unit and indoor unit, o
11 English7. When routing out the transmission wiring from the knockout hole.8.When routing out the power/ground wires from the right side.9. Power wi
English 1210. CHECKING OF DEVICE AND INSTAL-LATION CONDITIONSBe sure to check the followings.For those doing electrical work1.Make sure there is no fa
13 English[How to Check How Many Units are Connected]It is possible to find out how many indoor or outdoor unit in the system are turned on by operati
Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,Kita-ku, Osaka, 530-8323 JapanDAIKIN INDUSTRIES, LTD.EN60335-2-40,DAIKIN.TCF.024TNO05102601013P177868
English 1411-2-1 Procedure of Adding Refrigerant charging1.Make sure the following works are complete in accordance with the installation manual. Pip
15 EnglishBeware the fan running when open the front panel.The fan may continue rotation after the system stop the operation.(8) When the required amo
English 16[Remote controller displays malfunction code]NoteIf any malfunction codes other than the above are displayed, check the service manual for h
17 EnglishProcedure for checking maximum concentrationCheck the maximum concentration level in accordance with steps 1 to 4 below and take whatever ac
English 18NOTES01_EN_3P201178-4B.fm Page 18 Friday, May 18, 2007 7:58 PM
21figure 1figure 4figure 3≥1500314252(mm)≥1000≥1000≥1000≥1500≥1500≥15001figure 2≥10≥10≥10≥20≥20≥50≥50≥50≥200≥400 ≥400≥50≥10≥300 ≥300≥500≥500≥500≥500≥1
figure 19figure 221123453478296111281213151412349876510figure 17figure 18 TO IN/D UNIT TO OUT/D UNITF1 F2 F1 F21234A1P TO IN/D UNITF1 F2 F1 F2 TO OUT/
123425786figure 31figure 26 figure 27123456789101314151112: 18: 19(): 16: 1712132figure 25123101112456789(): 13: 14: 15: 163111210456798(): 13: 14: 15
3P201178-4B EM07A013(0705) HT00_CV_3P201178-4B.fm Page 5 Monday, May 21, 2007 9:09 AM
REYQ8PY1BREYQ10PY1BREYQ12PY1BREYQ14PY1BREYQ16PY1BVRVIII System air conditionerInstallation manual1 EnglishCONTENTS1. FIRST OF ALL ...
English 2• The indoor and BS unit should be installed as far away from fluo-rescent lighting as possible.Remote controller (wireless kit) transmitting
3 English2-2 Standard supplied accessoriesConfirm the following accessories are included. The storage location of the accessories is shown in figure 1