EDUS39-600-F3_b DimensionsFXSQ-M 9FXSQ24MVJU + BYBS71DJW1 (with Decoration Panel and Air Suction Canvas)3D042526
Dimensions EDUS39-600-F3_b10 FXSQ-MFXSQ30MVJU + BYBS125DJW1 (with Decoration Panel and Air Suction Canvas)FXSQ36MVJU + BYBS125DJW1 (with Decoration Pa
EDUS39-600-F3_b DimensionsFXSQ-M 11FXSQ12MVJU3D042520
Dimensions EDUS39-600-F3_b12 FXSQ-MFXSQ18MVJU3D042521
EDUS39-600-F3_b DimensionsFXSQ-M 13FXSQ24MVJU3D042522
Dimensions EDUS39-600-F3_b14 FXSQ-MFXSQ30MVJUFXSQ36MVJUFXSQ48MVJU3D042523
EDUS39-600-F3_b Piping DiagramsFXSQ-M 154. Piping DiagramsR1T : Thermistor for suction air temperatureR2T : Thermistor for liquid line temperatureR3T
Wiring Diagrams EDUS39-600-F3_b16 FXSQ-M5. Wiring DiagramsFXSQ12M/18M/24M/30M/36M/48MVJU3D043177A
EDUS39-600-F3_b Electric CharacteristicsFXSQ-M 176. Electric Characteristics
Capacity Tables EDUS39-600-F3_b18 FXSQ-M7. Capacity Tables7.1 Cooling CapacityFXSQ-MTC : Total capacity ; kWSHC : Sensible heat capacity ; kWRefer to
EDUS39-600-F3_bFXSQ-M 1FXSQ-MCeiling Mounted Built-In Type1. Features ...
EDUS39-600-F3_b Capacity TablesFXSQ-M 197.2 Heating CapacityFXSQ-MRefer to Outdoor Unit Capacity Tables for the actual performance data of each indoor
Capacity Tables EDUS39-600-F3_b20 FXSQ-MRefer to Outdoor Unit Capacity Tables for the actual performance data of each indoor and outdoor unit combinat
EDUS39-600-F3_b Fan PerformancesFXSQ-M 218. Fan PerformancesNote:1. The remote controller can be used to switch between HIGH and LOW. 2. The airflow
Sound Levels EDUS39-600-F3_b22 FXSQ-M9. Sound LevelsOverallOctave Band Level208V~230V Ceiling Mounted Built-In TypeNotes: Operation noise differs wit
EDUS39-600-F3_b InstallationFXSQ-M 2310.InstallationCenter of Gravity1. SAFETY CONSIDERATIONS Read these SAFETY CONSIDERATIONS carefully before insta
Installation EDUS39-600-F324 FXSQ-M• Do not touch the air outlet or the horizontal flaps while the swing flap is in operation as fingers may get caugh
EDUS39-600-F3 InstallationFXSQ-M 25• Dismantling of the unit, and treatment of the refriger-ant, oil, and other parts, should be done in accordance w
Installation EDUS39-600-F326 FXSQ-M2. BEFORE INSTALLATION• When moving the unit while removing it from the pack-ing case, be sure to lift it by the fo
EDUS39-600-F3 InstallationFXSQ-M 27Ta ble 2FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.a.
Installation EDUS39-600-F328 FXSQ-M• Install the indoor and outdoor units, power supply wir-ing, and connecting wires at least 3.5 ft. (1.1 m) away fr
Features EDUS39-600-F3_b2 FXSQ-M1. FeaturesA The Ceiling Mounted Built-In Type is a highly flexible air-conditioning system adaptable to a wide range
EDUS39-600-F3 InstallationFXSQ-M 29(3) Install the suspension bolts using bolts of 3/8” diameter.Use a hole-in-anchor, sunken insert, sunken anchor f
Installation EDUS39-600-F330 FXSQ-M6. REFRIGERANT PIPING WORK6-1 GENERAL INSTRUCTIONS• To install refrigerant piping to outdoor units, see the insta
EDUS39-600-F3 InstallationFXSQ-M 31CAUTION• Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed pip
Installation EDUS39-600-F332 FXSQ-M• If converging multiple drain pipes, install according to the procedure shown below.Select converging drain pipes
EDUS39-600-F3 InstallationFXSQ-M 338-2 ELECTRICAL CHARACTERISTICSMCA:Min. Circuit Amps (A); MFA:Max. Fuse Amps (A) kW: Fan Motor Rated Output (W); FLA
Installation EDUS39-600-F334 FXSQ-Mto the terminal block for remote control wiring or it could damange the entire system.• Improper installation ca
EDUS39-600-F3 InstallationFXSQ-M 359-2 SETTING OF STATIC PRESSURE CHANGEOVER CONNECTOR• According to the system static pressure requirement, repo-siti
Installation EDUS39-600-F3_b36 FXSQ-M9-3 WIRING EXAMPLE • Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing. COM
EDUS39-600-F3_b InstallationFXSQ-M 379-5 COMPUTERIZED CONTROL: FORCED OFF AND ON/OFF OPERATION(1) Wire specifications and how to perform wiring • Con
Installation EDUS39-600-F3_b38 FXSQ-M11. TEST OPERATION Refer to the installation manual of the outdoor unit.• The operation lamp of the remote contro
EDUS39-600-F3_b FeaturesFXSQ-M 3Example of Installation (Built-In) Direct installation of half panel Installation of half panel and suction canvas
EDUS39-600-F3_b AccessoriesFXSQ-M 3911.AccessoriesStandard AccessoriesOptional Accessories Note:+ If installing a high filter in the ceiling mounted b
EDUS 39 - 600 - F2AMERICASFXDQ-MSlim Ceiling Mounted Duct Type1645 Wallace Drive, Suite 110Carrollton, [email protected]
Features EDUS39-600-F3_b4 FXSQ-M Ceiling return Installation with duct (B)The access panel should be fitted beneath the main body of the unit.Model
EDUS39-600-F3_b SpecificationsFXSQ-M 52. SpecificationsCeiling Mounted Built-In TypeNotes:1. Nominal cooling capacities are based on the following con
Specifications EDUS39-600-F3_b6 FXSQ-MCeiling Mounted Built-In TypeNotes:1. Nominal cooling capacities are based on the following conditions: Return a
EDUS39-600-F3_b DimensionsFXSQ-M 73. DimensionsFXSQ12MVJU + BYBS32DJW1 (with Decoration Panel and Air Suction Canvas)3D042524
Dimensions EDUS39-600-F3_b8 FXSQ-MFXSQ18MVJU + BYBS45DJW1 (with Decoration Panel and Air Suction Canvas)3D042525