MODELSFTXZ25NV1BFTXZ35NV1BFTXZ50NV1BRXZ25NV1BRXZ35NV1BRXZ50NV1BINSTALLATIONMANUALR32 Split SeriesEnglishFrançaisEspañolItalianoΕλληνικάPyccкийTürkçeIn
884. Humidifying hose installation work4-1 Connecting to the indoor unit• Connect the cuff side of the G humidifying hose to the indoor unit duct.Du
99Indoor Unit Installation5. Laying piping, hoses, and wiring• Lay the pipes, drain hose and G humidifying hose according to the orientation of the p
10105-3 Wall embedded pipingFollow the instructions given under left-side, left-back, or left-bottom piping.1) Insert the drain hose to this depth s
1111Indoor Unit Installation7. Drain piping1) Connect the drain hose, as described right.The drain hose should be inclined downward.No trap is permi
1212Outdoor Unit Installation Guidelines• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airfl ow, follow the insta
1313Outdoor Unit Installation4. Refrigerant piping CAUTION• Use the fl are nut fi xed to the main unit. (To prevent cracking of the fl are nut by aged d
14146. Evacuating the air with a vacuum pump and checking gas leakage WARNING• Do not mix any substance other than the specifi ed refrigerant (R32) in
1515Outdoor Unit Installation7. Wiring WARNING• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, el
16168. Connecting the humidifying hose• If the air conditioner is operated without the G humidifying hose connected, humidifi ed air fi lls the outdoor
1717Installation Tips Removing and installing the front panel • Removal method 1) Hook your fi ngers on both sides of the front panel and open unti
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan DAIKIN INDUSTRIES, LTD.Low Voltage 2006/95/ECElectromagnetic Compatibility 2
1818• Installation method 1) Attach the front grille (bottom). Make sure that the tabs on both sides are securely hooked. (See Fig. 8)2) Attach the
1919Trial Operation and Testing1. Setting of the position where the indoor unit is installed• By setting the room shape and the relation with the ins
20203-3 To perform a trial operation for humidifying operation, activate trial operation mode from the remote controller following the instructions b
Two-dimensional bar code is a code for manufacturing.3P338604-1C M12B406B(1310) HT00_CV_3P338604-1C.indd 2 9/10/2013 1:30:12 PM
1ContentsSafety Precautions ... 2Accessories ... 4Choosing an Inst
2Safety PrecautionsRead the precautions in this manual carefully before operating the unit.This appliance is fi lled with R32.• The precautions descri
3Safety Precautions WARNING• Be sure to earth the air conditioner.Do not earth the unit to a utility pipe, lightning conductor or telephone earth lea
4AccessoriesIndoor unitAMounting plate1BPhotocatalytic air-purifying and deodorising fi lter1CIndoor unit fi xing screws (M4 × 12L)3DWireless remote con
5Choosing an Installation Site2. Wireless remote controller (When mounting on a wall etc.)• Turn on all the fl uorescent lamps in the room, if any, an
6Indoor/Outdoor Unit Installation DrawingsRefrigerant piping must be kept to a minimum.* The suggested shortest piping length is 1.5m, in order to av
77Indoor Unit Installation1. Installing the mounting plate• The A mounting plate is located at the back of the indoor unit. Remove a screw.• The A m