Service Manual[Applied Models]z Inverter Pair : Heat PumpInverter PairWall Mounted Type G-SeriesSiBE041029_A

Page 2 - G-Series

Introduction SiBE041029_Aix1.2 Used IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is de

Page 3 - Table of Contents ii

Troubleshooting SiBE041029_A90 Service Diagnosis4.23 Electrical Box Temperature RiseError CodeL3Method of Error DetectionAn electrical box temperature

Page 4

SiBE041029_A TroubleshootingService Diagnosis 914.24 Radiation Fin Temperature RiseError CodeL4Method of Error DetectionA radiation fin temperature ri

Page 5 - Table of Contents iv

Troubleshooting SiBE041029_A92 Service DiagnosisTroubleshootingCheck No.17Refer to P.101Check No.19Refer to P.102Note: Refer to “Silicon Grease on Pow

Page 6 - 1. Introduction

SiBE041029_A TroubleshootingService Diagnosis 934.25 Output Overcurrent DetectionError CodeL5Method of Error DetectionAn output overcurrent is detecte

Page 7

Troubleshooting SiBE041029_A94 Service DiagnosisTroubleshootingCheck No.15Refer to P.99Check No.17Refer to P.101Check No.18Refer to P.101Check No.22Re

Page 8

SiBE041029_A CheckService Diagnosis 955. Check5.1 Thermistor Resistance CheckCheck No.01 Disconnect the connectors of the thermistors from the PCB, an

Page 9

Check SiBE041029_A96 Service Diagnosis5.2 Fan Motor Connector Output CheckCheck No.02 1. Check the connection of connector.2. Check the motor power su

Page 10 - 1.2 Used Icons

SiBE041029_A CheckService Diagnosis 975.4 Electronic Expansion Valve CheckCheck No.12 Conduct the followings to check the electronic expansion valve (

Page 11 - List of Functions

Check SiBE041029_A98 Service Diagnosis5.5 Four Way Valve Performance CheckCheck No.135.6 Inverter Units Refrigerant System CheckCheck No.14(R15737)NOY

Page 12 - 1. Functions

SiBE041029_A CheckService Diagnosis 995.7 Inverter Analyzer CheckCheck No.15CharacteristicsInverter analyzer: RSUK0917CIf an abnormal stop occurs due

Page 13

SiBE041029_AList of Functions 1Part 1List of Functions1. Functions...

Page 14 - Specifications

Check SiBE041029_A100 Service DiagnosisDiagnose method (Diagnose according to 6 LEDs lighting status.)(1) If all the LEDs are lit uniformly, the comp

Page 15 - 1. Specifications

SiBE041029_A CheckService Diagnosis 1015.9 Installation Condition CheckCheck No.175.10 Discharge Pressure CheckCheck No.18Installation condition check

Page 16 - 50 Hz, 220 - 230 - 240V

Check SiBE041029_A102 Service Diagnosis5.11 Outdoor Fan System CheckCheck No.19 DC motor5.12 Main Circuit Short CheckCheck No.20 RX50/60G3V1B onlyNote

Page 17 - 50 Hz, 220 - 230 - 240 V

SiBE041029_A CheckService Diagnosis 1035.13 Capacitor Voltage CheckCheck No.21 RX50/60G2V1B, 71 class onlyBefore this check, be sure to check the main

Page 18

Check SiBE041029_A104 Service DiagnosisRX50/60G2V1B, 71 class The illustration is for 71 class as representative.RX50/60G3V1B(R16073)Power modulePowe

Page 19 - Connector Wiring Diagram

SiBE041029_ATrial Operation and Field Settings 105Part 7Trial Operation andField Settings1. Pump Down Operation...

Page 20 - 1. Indoor Unit

Pump Down Operation SiBE041029_A106 Trial Operation and Field Settings1. Pump Down OperationOutline In order to protect the environment, be sure to co

Page 21 - SiBE041029_A Indoor Unit

SiBE041029_A Forced Cooling OperationTrial Operation and Field Settings 1072. Forced Cooling OperationIndoor UnitOutdoor Unit: RX50/60G2V1B, 71 class+

Page 22 - 2. Outdoor Unit

Trial Operation SiBE041029_A108 Trial Operation and Field Settings3. Trial OperationOutline 1. Measure the power supply voltage and make sure that it

Page 23 - SiBE041029_A Outdoor Unit

SiBE041029_A Field SettingsTrial Operation and Field Settings 1094. Field Settings4.1 When 2 Units are Installed in 1 RoomOutline When 2 indoor units

Page 24 - 2.2 RX50/60G3V1B

Functions SiBE041029_A2 List of Functions1. FunctionsCategory FunctionsFTX50/60/71GV1BRX50/60G2V1BRX71GV1BCategory FunctionsFTX50/60/71GV1BRX50/60G2V1

Page 25

Field Settings SiBE041029_A110 Trial Operation and Field Settings4.2 Facility Setting Switch (cooling at low outdoor temperature)Outline This function

Page 26 - Function and Control

SiBE041029_A Field SettingsTrial Operation and Field Settings 1114.3 Jumper and Switch SettingsIndoor UnitFor the location of the jumper, refer to pag

Page 27 - 1. Main Functions

Silicon Grease on Power Transistor / Diode Bridge SiBE041029_A112 Trial Operation and Field Settings5. Silicon Grease on Power Transistor / Diode Brid

Page 28

SiBE041029_AAppendix 113Part 8Appendix1. Piping Diagrams...1141.1 Indoo

Page 29 - 1.3 Airflow Direction Control

Piping Diagrams SiBE041029_A114 Appendix1. Piping Diagrams1.1 Indoor Unit1.2 Outdoor UnitRX50/60G2V1BFTX50/60GV1B FTX71GV1BFIELD PIPINGFIELD PIPING(12

Page 30 - (R12390)

SiBE041029_A Piping DiagramsAppendix 115RX50/60G3V1BRX71GV1B, RX71GV1B9OUTDOOR UNITHEAT EXCHANGER7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT12.7CuTCAPILLARY TUBE 1

Page 31 - 1.5 Program Dry Operation

Wiring Diagrams SiBE041029_A116 Appendix2. Wiring Diagrams2.1 Indoor UnitFTX50/60/71GV1B2.2 Outdoor UnitRX50G2V1BPCB4PCB3PCB5LED1H1PR1TtS37S38°LED2H2P

Page 32 - 1.6 Automatic Operation

SiBE041029_A Wiring DiagramsAppendix 117RX60G2V1BRX50/60G3V1BINDOORSA2OUTDOORX1MSHEET METALGRNYLWFIELD WIRINGS10MRM10WHTLBLUY1EPCB1BRNS90R2TWVYLWE2BLU

Page 33 - 1.7 Thermostat Control

Wiring Diagrams SiBE041029_A118 AppendixRX71GV1B, RX71GV1B9L1RGRNZ7CGRNYLWZ1CX1MZ6CBLUFU3WHTGRN7REDM1FE1E2LHR2SA2HR1MRM203.15APOWER SUPPLYV100MV2Z2CAC

Page 34 - 1.8 NIGHT SET Mode

SiBE041029_A Removal Procedure (Booklet No.)Appendix 1193. Removal Procedure (Booklet No.)Refer to the following booklets for removal procedure.∗FTX50

Page 35 - 1.9 HOME LEAVE Operation

SiBE041029_A FunctionsList of Functions 3Category FunctionsFTX50/60/71GV1BRX50/60G3V1BRX71GV1B9Category FunctionsFTX50/60/71GV1BRX50/60G3V1BRX71GV1B9B

Page 36

Revision HistoryMonth / Year Version Revised contents03 / 2010 SiBE041029 First edition12 / 2012 SiBE041029_A Model addition: RX50/60G3V1B, RX71GV1B9

Page 37 - Function and Control 27

Head Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 JapanTokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, To

Page 38 - POWERFUL

SiBE041029_A4 SpecificationsPart 2Specifications1. Specifications ...

Page 39 - 1.12 Clock Setting

SiBE041029_A SpecificationsSpecifications 51. Specifications50 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table bel

Page 40 - 1.13 Other Functions

Specifications SiBE041029_A6 Specifications50 Hz, 220 - 230 - 240VNote: The data are based on the conditions shown in the table below.ModelIndoor Uni

Page 41 - 2. Function of Thermistor

SiBE041029_A SpecificationsSpecifications 750 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.ModelIndoor Un

Page 42 - 3. Control Specification

Specifications SiBE041029_A8 Specifications50 Hz, 220 - 230 - 240VNote: The data are based on the conditions shown in the table below.ModelIndoor Uni

Page 43 - 3.2 Frequency Control

SiBE041029_APrinted Circuit Board Connector Wiring Diagram 9Part 3Printed Circuit BoardConnector Wiring Diagram1. Indoor Unit...

Page 44

SiBE041029_Ai Table of ContentsInverter PairWall Mounted TypeG-SerieszHeat PumpIndoor UnitFTX50GV1BFTX60GV1BFTX71GV1BOutdoor UnitRX50G2V1B RX50G3V1BRX

Page 45 - 3.3.1 Preheating Control

Indoor Unit SiBE041029_A10 Printed Circuit Board Connector Wiring Diagram1. Indoor UnitPCB (1): Control PCBCaution Replace the PCB if you accidentally

Page 46 - 3.3.4 3-minute Standby

SiBE041029_A Indoor UnitPrinted Circuit Board Connector Wiring Diagram 11PCB (2): Signal Receiver PCBPCB (3): Buzzer PCBPCB (4): Display PCBPCB (5): I

Page 47 - (R14642)

Outdoor Unit SiBE041029_A12 Printed Circuit Board Connector Wiring Diagram2. Outdoor Unit2.1 RX50/60G2V1B, 71 ClassPCB (1): Main PCBRX50/60G2V1B1) S10

Page 48 - 3.5 Input Current Control

SiBE041029_A Outdoor UnitPrinted Circuit Board Connector Wiring Diagram 1371 classPCB (2): Service Monitor PCB SW4-A has no function. Keep it OFF.V3A

Page 49 - 3.7 Heating Peak-cut Control

Outdoor Unit SiBE041029_A14 Printed Circuit Board Connector Wiring Diagram2.2 RX50/60G3V1BPCB (1): Filter PCB1) S11 Connector for [S10] on main PCB2)

Page 50 - 3.8 Outdoor Fan Control

SiBE041029_A Outdoor UnitPrinted Circuit Board Connector Wiring Diagram 15PCB (2): Main PCBCaution Replace the PCB if you accidentally cut the jumpers

Page 51 - 3.10 Defrost Control

SiBE041029_A16 Function and ControlPart 4Function and Control1. Main Functions...

Page 52 - 42 Function and Control

SiBE041029_A Main FunctionsFunction and Control 171. Main Functions1.1 Temperature ControlDefinitions of TemperaturesThe definitions of temperatures a

Page 53 - Minimum opening (pulse) 54 75

Main Functions SiBE041029_A18 Function and ControlDrawing of InverterThe following drawing shows a schematic view of the inverter principle:Inverter F

Page 54 - (R14213)

SiBE041029_A Main FunctionsFunction and Control 191.3 Airflow Direction ControlPower-Airflow Dual FlapsThe large flap sends a large volume of air down

Page 55 - 3.12 Malfunctions

SiBE041029_ATable of Contents ii1. Introduction ...v1.1 Safe

Page 56 - Remote Controller

Main Functions SiBE041029_A20 Function and Control1.4 Fan Speed Control for Indoor UnitOutline Phase control and fan speed control contains 9 steps: L

Page 57 - 1. FTX50/60/71GV1B

SiBE041029_A Main FunctionsFunction and Control 211.5 Program Dry OperationOutline Program dry operation removes humidity while preventing the room te

Page 58 - (R18205)

Main Functions SiBE041029_A22 Function and Control1.6 Automatic OperationOutline Automatic Cooling / Heating FunctionWhen the automatic operation is s

Page 59 - Service Diagnosis

SiBE041029_A Main FunctionsFunction and Control 231.7 Thermostat ControlOutline Thermostat control is based on the difference between the room thermis

Page 60 - 50 Service Diagnosis

Main Functions SiBE041029_A24 Function and Control1.8 NIGHT SET ModeOutline When the OFF TIMER is set, the NIGHT SET Mode is automatically activated.

Page 61 - 1. Troubleshooting with LED

SiBE041029_A Main FunctionsFunction and Control 251.9 HOME LEAVE OperationOutline HOME LEAVE operation is a function that allows you to record your fa

Page 62

Main Functions SiBE041029_A26 Function and ControlHow to Set the Temperature and Airflow RateWhen using HOME LEAVE operation for the first time, set t

Page 63 - Timer cancel button

SiBE041029_A Main FunctionsFunction and Control 271.10 INTELLIGENT EYE OperationOutline This function detects the existence of humans in the room with

Page 64 - (R14968)

Main Functions SiBE041029_A28 Function and Control1.11 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full

Page 65 - (R14969)

SiBE041029_A Main FunctionsFunction and Control 291.12 Clock SettingARC433 Series The clock can be set by taking the following steps:1. Press the [CLO

Page 66 - 4. Troubleshooting

SiBE041029_Aiii Table of ContentsPart 6 Service Diagnosis... 491. Troubleshooting with LED .

Page 67 - Model Type Connector

Main Functions SiBE041029_A30 Function and Control1.13 Other Functions1.13.1 Hot-Start FunctionIn order to prevent the cold air blast that normally co

Page 68 - 58 Service Diagnosis

SiBE041029_A Function of ThermistorFunction and Control 312. Function of Thermistor(1) Outdoor Heat Exchanger Thermistor 1. The outdoor heat exchang

Page 69 - Service Diagnosis 59

Control Specification SiBE041029_A32 Function and Control3. Control Specification3.1 Mode HierarchyOutline Air conditioner control has normal operatio

Page 70 - Refer to P.96

SiBE041029_A Control SpecificationFunction and Control 333.2 Frequency ControlOutline Frequency is determined according to the difference between the

Page 71 - Service Diagnosis 61

Control Specification SiBE041029_A34 Function and ControlIndoor Frequency Command (∆D signal)The difference between the room thermistor temperature an

Page 72 - 4.6 Refrigerant Shortage

SiBE041029_A Control SpecificationFunction and Control 353.3 Controls at Mode Changing / Start-up3.3.1 Preheating ControlOutline The inverter operatio

Page 73 - Refer to P.97

Control Specification SiBE041029_A36 Function and Control3.3.3 Four Way Valve Operation CompensationOutline At the beginning of the operation as the f

Page 74 - 64 Service Diagnosis

SiBE041029_A Control SpecificationFunction and Control 373.4 Discharge Pipe Temperature ControlOutline The discharge pipe temperature is used as the i

Page 75

Control Specification SiBE041029_A38 Function and Control3.5 Input Current ControlOutline The microcomputer calculates the input current while the com

Page 76 - Outdoor Unit)

SiBE041029_A Control SpecificationFunction and Control 393.6 Freeze-up Protection ControlOutline During cooling operation, the signal sent from the in

Page 77 - Check No.11

SiBE041029_ATable of Contents ivPart 7 Trial Operation and Field Settings... 1051. Pump Down Operation...

Page 78 - (RX50/60G2V1B, 71 Class Only)

Control Specification SiBE041029_A40 Function and Control3.8 Outdoor Fan Control1. Fan ON control to cool down the electrical boxThe outdoor fan is tu

Page 79 - Service Diagnosis 69

SiBE041029_A Control SpecificationFunction and Control 413.10 Defrost ControlOutline Defrosting is carried out by the cooling cycle (reverse cycle). T

Page 80 - 70 Service Diagnosis

Control Specification SiBE041029_A42 Function and Control3.11 Electronic Expansion Valve ControlOutline The following items are included in the electr

Page 81 - Troubleshooting RX50/60G3V1B

SiBE041029_A Control SpecificationFunction and Control 433.11.1 Fully Closing with Power ONThe electronic expansion valve is initialized when turning

Page 82 - 72 Service Diagnosis

Control Specification SiBE041029_A44 Function and Control3.11.7 Control for Disconnection of the Discharge Pipe ThermistorOutline The disconnection of

Page 83 - Service Diagnosis 73

SiBE041029_A Control SpecificationFunction and Control 453.12 Malfunctions3.12.1 Sensor Malfunction DetectionSensor malfunction may occur in the therm

Page 84 - 4.13 Compressor Lock

SiBE041029_A46 Remote ControllerPart 5Remote Controller1. FTX50/60/71GV1B...

Page 85 - 4.14 DC Fan Lock

SiBE041029_A FTX50/60/71GV1BRemote Controller 471. FTX50/60/71GV1BReference Refer to the following pages for detail.Note: Refer to the operation manu

Page 86 - 76 Service Diagnosis

FTX50/60/71GV1B SiBE041029_A48 Remote ControllerOpen the Front CoverReference Refer to the following pages for detail.Note: Refer to the operation man

Page 87 - Service Diagnosis 77

SiBE041029_AService Diagnosis 49Part 6Service Diagnosis1. Troubleshooting with LED ...

Page 88 - 78 Service Diagnosis

Introduction SiBE041029_Av1. Introduction1.1 Safety CautionsCautions and WarningsBe sure to read the following safety cautions before conducting repa

Page 89 - 71 class 120 107

SiBE041029_A50 Service Diagnosis5.13 Capacitor Voltage Check...1035.14 Power Module

Page 90 - 80 Service Diagnosis

SiBE041029_A Troubleshooting with LEDService Diagnosis 511. Troubleshooting with LED1.1 Indoor UnitOperation Lamp The operation lamp blinks when any o

Page 91 - 4.19.1 RX50/60G2V1B, 71 Class

Problem Symptoms and Measures SiBE041029_A52 Service Diagnosis2. Problem Symptoms and MeasuresSymptom Check Item Details of Measure ReferencePageThe u

Page 92 - 4.19.2 RX50/60G3V1B

SiBE041029_A Service Check FunctionService Diagnosis 533. Service Check FunctionCheck Method 1 1. When the timer cancel button is held down for 5 seco

Page 93 - Service Diagnosis 83

Service Check Function SiBE041029_A54 Service DiagnosisCheck Method 21. Press the center of the [TEMP] button and the [MODE] button at the same time t

Page 94 - Refer to P.101

SiBE041029_A Service Check FunctionService Diagnosis 555. Press the [TEMP]  or  button and change the number until you hear the long beep.6. Diagnos

Page 95 - Service Diagnosis 85

Troubleshooting SiBE041029_A56 Service Diagnosis4. Troubleshooting4.1 Error Codes and Description: Displayed only when system-down occurs.Error Codes

Page 96 - 71 class 32 0.5

SiBE041029_A TroubleshootingService Diagnosis 574.2 Indoor Unit PCB AbnormalityError CodeA1Method of Error DetectionThe system checks if the circuit w

Page 97 - Refer to P.103

Troubleshooting SiBE041029_A58 Service Diagnosis4.3 Freeze-up Protection Control or Heating Peak-cut ControlError CodeA5Method of Error DetectionFree

Page 98 - 88 Service Diagnosis

SiBE041029_A TroubleshootingService Diagnosis 594.4 Fan Motor (DC Motor) or Related AbnormalityError CodeA6Method of Error DetectionThe rotation speed

Page 99 - Service Diagnosis 89

SiBE041029_A IntroductionviBe sure to wear a safety helmet, gloves, and a safety belt when working at a high place (more than 2 m). Insufficient safet

Page 100 - (R14444)

Troubleshooting SiBE041029_A60 Service DiagnosisTroubleshootingCheck No.02Refer to P.96Turn off the power supply and disconnect the fan motor connecto

Page 101

SiBE041029_A TroubleshootingService Diagnosis 614.5 Thermistor or Related Abnormality (Indoor Unit)Error CodeC4, C9 Method of Error DetectionThe temp

Page 102 - (R18185)

Troubleshooting SiBE041029_A62 Service Diagnosis4.6 Refrigerant ShortageError CodeU0Method of Error DetectionRefrigerant shortage detection I:Refriger

Page 103 - Service Diagnosis 93

SiBE041029_A TroubleshootingService Diagnosis 63TroubleshootingCheck No.01Refer to P.95Check No.12Refer to P.97(R16015)CautionYESNGNONOYESYESYESNOYESN

Page 104 - 94 Service Diagnosis

Troubleshooting SiBE041029_A64 Service Diagnosis4.7 Low-voltage Detection or Over-voltage DetectionError CodeU2Method of Error DetectionLow-voltage de

Page 105 - 5. Check

SiBE041029_A TroubleshootingService Diagnosis 65TroubleshootingCorrect the power supply.Replace the outdoor unit PCB.Check for such factors for a long

Page 106 - Check SiBE041029_A

Troubleshooting SiBE041029_A66 Service Diagnosis4.8 Signal Transmission Error (between Indoor Unit and Outdoor Unit)Error CodeU4Method of Error Detect

Page 107 - Service Diagnosis 97

SiBE041029_A TroubleshootingService Diagnosis 67TroubleshootingCheck No.11Refer to P.96Check No.11Check the power supply waveform.Check the voltage of

Page 108 - Check No.14

Troubleshooting SiBE041029_A68 Service Diagnosis4.9 Signal Transmission Error on Outdoor Unit PCB (RX50/60G2V1B, 71 Class Only)Error CodeU7Method of E

Page 109 - 5.7 Inverter Analyzer Check

SiBE041029_A TroubleshootingService Diagnosis 694.10 Unspecified Voltage (between Indoor Unit and Outdoor Unit)Error Code UAMethod of Error Detection

Page 110 - (R10811)

Introduction SiBE041029_Avii1.1.2 Cautions Regarding Safety of UsersWarningBe sure to use parts listed in the service parts list of the applicable mod

Page 111 - 5.10 Discharge Pressure Check

Troubleshooting SiBE041029_A70 Service Diagnosis4.11 Outdoor Unit PCB AbnormalityError Code E1Method of Error DetectionThe system checks if the micr

Page 112 - 5.12 Main Circuit Short Check

SiBE041029_A TroubleshootingService Diagnosis 71Troubleshooting RX50/60G3V1BCautionBe sure to turn off the power switch before connecting or disconnec

Page 113 - 5.14 Power Module Check

Troubleshooting SiBE041029_A72 Service Diagnosis4.12 OL Activation (Compressor Overload)Error CodeE5Method of Error DetectionA compressor overload is

Page 114 - (R16692)

SiBE041029_A TroubleshootingService Diagnosis 73TroubleshootingCheck No.01Refer to P.95Check No.12Refer to P.97Check No.13Refer to P.98Check No.14Refe

Page 115 - Field Settings

Troubleshooting SiBE041029_A74 Service Diagnosis4.13 Compressor LockError CodeE6Method of Error DetectionA compressor lock is detected by checking the

Page 116 - 1. Pump Down Operation

SiBE041029_A TroubleshootingService Diagnosis 754.14 DC Fan LockError CodeE7Method of Error DetectionAn error is determined with the high-voltage fan

Page 117 - 2. Forced Cooling Operation

Troubleshooting SiBE041029_A76 Service Diagnosis4.15 Input Overcurrent DetectionError CodeE8Method of Error DetectionAn input overcurrent is detected

Page 118 - (2) (3) (4)

SiBE041029_A TroubleshootingService Diagnosis 774.16 Four Way Valve AbnormalityError CodeEAMethod of Error DetectionThe room temperature thermistor an

Page 119 - 4. Field Settings

Troubleshooting SiBE041029_A78 Service DiagnosisTroubleshootingCheck No.01Refer to P.95Check No.13Refer to P.98Check No.14Refer to P.98NGOKNOOKNGOKYES

Page 120 - Field Settings SiBE041029_A

SiBE041029_A TroubleshootingService Diagnosis 794.17 Discharge Pipe Temperature ControlError CodeF3Method of Error DetectionAn error is determined wit

Page 121

SiBE041029_A IntroductionviiiCheck to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet securely.If

Page 122 - (R18017)

Troubleshooting SiBE041029_A80 Service Diagnosis4.18 High Pressure Control in CoolingError CodeF6Method of Error DetectionHigh-pressure control (opera

Page 123 - Appendix

SiBE041029_A TroubleshootingService Diagnosis 814.19 Compressor System Sensor Abnormality4.19.1 RX50/60G2V1B, 71 ClassError CodeH0Method of Error Dete

Page 124 - 1. Piping Diagrams

Troubleshooting SiBE041029_A82 Service Diagnosis4.19.2 RX50/60G3V1BError Code H0Method of Error DetectionThe system checks the DC current before the

Page 125 - RX71GV1B, RX71GV1B9

SiBE041029_A TroubleshootingService Diagnosis 834.20 Position Sensor AbnormalityError CodeH6Method of Error DetectionA compressor start-up failure is

Page 126 - 2. Wiring Diagrams

Troubleshooting SiBE041029_A84 Service DiagnosisTroubleshooting RX50/60G2V1B, 71 classCheck No.15Refer to P.99Check No.18Refer to P.101CautionBe sure

Page 127 - RX60G2V1B

SiBE041029_A TroubleshootingService Diagnosis 85Troubleshooting RX50/60G3V1BCheck No.15Refer to P.99Check No.18Refer to P.101Check No.20Refer to P.102

Page 128

Troubleshooting SiBE041029_A86 Service Diagnosis4.21 CT or Related Abnormality (RX50/60G2V1B, 71 Class Only)Error CodeH8Method of Error DetectionA CT

Page 129

SiBE041029_A TroubleshootingService Diagnosis 87TroubleshootingCheck No.15Refer to P.99Check No.21Refer to P.103(R18341)CautionYES2 secTimeNONOYESYESN

Page 130 - Revision History

Troubleshooting SiBE041029_A88 Service Diagnosis4.22 Thermistor or Related Abnormality (Outdoor Unit)Error Code H9, J3, J6, P4Method of Error Detectio

Page 131 - All rights reserved

SiBE041029_A TroubleshootingService Diagnosis 89Troubleshooting In case of “H9” “J3” “J6”Check No.01Refer to P.95H9 : Outdoor temperature thermistorJ3