Daikin FFQ35C Datasheet Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
7
Multi model application
• A single multi outdoor unit can power up nine indoor units in different rooms. Of course, the
climate of each room is individually controlled.
• This assures top efficiency and optimum comfort for each separate space.
Fully integrated solutions for medium to large commercial environments connecting up to 64 indoor units to a single
system, all individually controlled.
• Perfect comfort by simultaneous heating spaces, while cooling others
• Free heating of rooms or water possible by heat recovery
• Temperature control, fresh air, air curtains and hot water production all integrated in a single system
INDOOR UNIT FXZQ15A FXZQ20A FXZQ25A FXZQ32A FXZQ40A FXZQ50A
Cooling capacity Nom. kW
1.7 2.2 2.8 3.6 4.5 5.6
Heating capacity
Nom. kW 1.9 2.5 3.2 4.0 5.0 6.3
Power input - 50Hz
Cooling Nom. kW 0.043 0.045 0.059 0.092
Heating Nom. kW 0.036 0.038 0.053 0.086
Dimensions
Unit HeightxWidthxDepth mm 260x575x575
Weight
Unit kg 15.5 16.5 18.5
Decoration panel
Model BYFQ60CW / BYFQ60CS / BYFQ60B2
Colour White (N9.5) / White (N9.5) + Silver / White (RAL9010)
Dimensions HeightxWidthxDepth mm 46x620x620 / 46x620x620 / 55x700x700
Weight kg 2.8 / 2.8 / 2.7
Fan-Air ow rate
- 50Hz
Cooling High/Nom./Low m³/min 8.5/7/6.5 8.7/7.5/6.5 9/8/6.5 10/8.5/7 11.5/9.5/8 14.5/12.5/10
Heating High/Nom./Low m³/min 8.5/7/6.5 8.7/7.5/6.5 9/8/6.5 10/8.5/7 11.5/9.5/8 14.5/12.5/10
Sound power level
Cooling High/Nom. dBA 49/- 50/- 51/- 54/- 60/-
Sound pressure
level
Cooling High/Nom./Low dBA 31.5/28/25.5 32/29.5/25.5 33/30/25.5 33.5/30/26 37/32/28 43/40/33
Heating High/Nom./Low dBA 31.5/28/25.5 32/29.5/25.5 33/30/25.5 33.5/30/26 37/32/28 43/40/33
Refrigerant
Type R-410A
Piping connections
Liquid/OD/Gas/OD/Drain mm 6.35/12.7/VP20 (I.D. 20/O.D. 26)
Power supply
Phase/Frequency/Voltage Hz/V 1~/50/220-240
Current - 50Hz Maximum fuse amps (MFA) A 16
For more information on combination, please refer to the VRV catalogue.
Twin, triple, double twin
Heating & Cooling, Heat Recovery
• For long or irregularly shaped rooms you can use up to four indoor units powered by a
single outdoor unit.
• All indoor units are controlled at the same time.
FFQ-C
OUTDOOR UNIT 35 50 60
Seasonal
Smart
RZQG71L8V1 RZQG71L8Y1
• operation in heating mode
down to -20°C
• 75m pipe run
• Compatibility with D-BACS
2
RZQG100L8V1 RZQG100L8Y1 3 2
RZQG125L8V1 RZQG125L8Y1 4 3 2
RZQG140L7V1 RZQG140LY1 4 3
RZQ200C
• operation in heating mode
down to -15°C
• 100m pipe run
- 4 3
RZQ250C - 4
RZQSG71L3V1
• operation in heating mode
down to -15°C
• 50m pipe run
• Compatibility with D-BACS
2
RZQSG100L8V1 RZQSG100L8Y1 3 2
RZQSG125L8V1 RZQSG125L8Y1 4 3 2
RZQSG140LV1 RZQSG140LY1 4 3
OUTDOOR UNIT
25 35 50 60
2MXS50H
3MXS40K
3MXS52E
3MXS68G
4MXS68F
4MXS80E
5MXS90E
RXYSQ-P8V1