Daikin FFQ12LVJU User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
4 www.daikincomfort.com SS-MXS
SS-MXS www.daikincomfort.com 5
Dimensions Slim-Duct Indoor Units
FDXS09/12LVJU
SIGNAL TRANSMITTER
11/16 (18mm)
2-5/16 (58mm)
7-3/8 (187mm)
PROTECTION NET
10
AIR FILTER (ACCESSORY)
9
SUSPENSION BRACKET
8
POWER SUPPLY CONNECTION
7
INFRARED RECEIVER UNIT CONNECTION
6
CONTROL BOX
5
DRAIN HOSE (ACCESSORY)
4
I.D. φ31/32(φ25mm) (OUTLET)
SOCKET FOR DRAIN
VP20 (O.D. φ1-1/32 (φ26mm)/ I.D. φ25/32 (φ20mm))
3
GAS PIPE CONNECTION
2
LIQUID PIPE CONNECTION
1
φ1/4 (φ6.4mm) (FLARE CONNECTION)
φ3/8 (φ9.5mm) (FLARE CONNECTION)
NUMBER
DESCRIPTIONNAME
12(300mm) OR MORE
27-9/16(700mm)
(SERVICE SPACE)
24-7/16
(1-3/4) (45mm)
(620mm)
15-3/4 (400mm) OR MORE
9-1/2(240mm) OR MORE
13/16 (20mm) OR MORE
(13/16)
1-1/2 (38mm)
2-3/4
ROOM TEMP.
SENSOR
(SUSPENSION BOLT PITCH)
(20mm)
(70mm)
27-9/16
(700mm)
OPERATION LAMP
24-7/16(620mm)
19-11/16 (500mm)
TIMER LAMP
4-3/4 (120mm)
CEILING
8
INDOOR UNIT
ON/OFF SWITCH
(300mm)
11-13/16
SIGNAL RECEIVER
<<
SERVICE SPACE
>>
16-φ 3/16 (φ4.7mm)
5x(P3-15/16)=19-11/16
HOLE
(2-13/16) (72mm)
(P100mm)
INFRARED RECEIVER UNIT
(ALL AROUND)
ARROW VIEW
13/16 (20mm) OR MORE
2-3/8 (60mm)
29-1/8 (740mm)
INSPECTION DOOR
(CEILING OPENING)
(SUSPENSION BOLT PITCH)
16-M5 HOLES
SUSPENSION BOLT
(ALL AROUND)
5-1/8 (130mm)
3-9/16 (90mm) 23-5/8 (600mm)
26-3/4 (680mm)
2-1/2 (63mm)
26 (660mm)
22-13/16 (580mm)3-15/16 (100mm)
13/16 (20mm)
1-15/16 (50mm)
4x(P5-7/8)=23-5/8
2-1/4 (57.5mm)
3/8 (10mm)
13/16 (21mm)
1/2 (12.5mm)
10
12
(P150mm) (600mm)
9
4
7
1-3/16 (30mm)
14-M4 HOLES
5-1/2 (140mm)
5x(P3-15/16)=19-11/16
(ALL AROUND)
(P100mm) (500mm)
7/8 (23mm)
3
5
6 (153mm)
13 (330mm)
3-1/8 (80mm)
3-15/16 (100mm)
24-7/16 (620mm)
3-1/8 (80mm)
3-15/16 (100mm)
6-5/16 (160mm)
6-11/16 (170mm)
7-7/8 (200mm)
6-11/16 (170mm)
7-1/16 (180mm)
<<
IN CASE OF BACK-SUCTION
>>
(620mm)24-7/16
(600mm)23-5/8
9
7-1/16 (180mm)
6-5/16 (160mm)
3-15/16 (100mm)
7-7/8 (200mm)
6
3-1/8 (80mm)
10
3-9/16 (90mm)
3/8 (10mm)
5x(P3-15/16)=19-11/16
5-1/2 (140mm)
13/16 (20mm)
1-15/16 (50mm)
(P100mm) (500mm)
3-15/16 (100mm)
22-13/16 (580mm)
16-M5 HOLES
<<
IN CASE OF BOTTOM-SUCTION
>>
(ALL AROUND)
WIRELESS REMOTE CONTROLLER
(ARC452A23)
4-M8~M10
1. IN CASE OF BACK-SUCTION, MOUNT
CHAMBER COVER TO BOTTOM SIDE OF THE UNIT.
IN CASE OF BOTTOM-SUCTION,
MOUNT CHAMBER COVER TO BACK SIDE OF THE UNIT.
2. LOCATION OF UNIT'S NAME PLATE: CONTROL BOX COVER
3. MOUNT THE AIR FILTER AT THE SUCTION SIDE.
SELECT ITS COLORIMETHOD (GRAVITY METHOD)
50% OR MORE.
IT CAN NOT BE EQUIPPED WITH AIR FILTER (ACCESSORY)
WHEN CONNECTING DUCT TO SUCTION SIDE.
4. PIPE SPECIFICATION
NOTE)
)(
CORD (LENGTH: 74-13/16)
( : 1900mm)
3-9/16 (90mm)
1-7/8 (47mm)
(500mm)
3D074619
CDXS15/18LVJU
11-13/16 (300mm) OR MORE
35-7/16 (900mm)
24-7/16 (620mm)
(SERVICE SPACE)
15-3/4 (400mm) OR MORE
(1-3/4) (45mm)
13/16 (20mm) OR MORE
SIGNAL TRANSMITTER
11/16 (18mm)
2-5/16 (58mm)
13/16 (20mm) OR MORE
(13/16)
1-1/2 (38mm)
2-3/4
ROOM TEMP.
35-7/16 (900mm)
SENSOR
(20mm)
(70mm)
24-7/16 (620mm)
19-11/16 (500mm)
OPERATION LAMP
(SUSPENSION BOLT PITCH)
CEILING
TIMER LAMP
4-3/4 (120mm)
< SERVICE SPACE >
(ALL AROUND)
INDOOR UNIT
7-3/8 (187mm)
22-φ 3/16 (φ 4.7mm) HOLES
ON/OFF SWITCH
9-1/2 (240mm) OR MORE
8
8xP.3-15/16 (100mm)=31-1/2 (800mm)
SIGNAL RECEIVER
CORD (LENGTH: 74-13/16)
37 (940mm)
( :1900mm)
(SUSPENSION BOLT PITCH)
2-3/8 (60mm)
(2-13/16) (72mm)
INFRARED RECEIVER UNIT
WIRELESS REMOTE CONTROLLER
34-5/8 (880mm)
(ARC452A23)
5-1/8 (130mm)
2-1/2 (63mm)
33-7/8 (860mm)
ARROW VIEW
3-9/16 (90mm)
3-9/16 (90mm)
4xP.5-7/8 (150mm)=23-5/8 (600mm)
INSPECTION DOOR
11-13/16 (300mm)
(CEILING OPENING)
SUSPENSION BOLT
2 1
4-UNC5/16 ~ 3/8
3-9/16 (90mm)
1-7/8 (47mm)
(M8 ~ M10)
20-M5 HOLES
1-15/16 (50mm)
13/16 (20mm)
2-1/4 (57.5mm)
13/16 (21mm)
3/8 (10mm)
1/2 (12.5mm)
10
(ALL AROUND)
6 (153mm)
6-5/16 (160mm)
7-1/16 (180mm)
7-7/8 (200mm)
6-11/16 (170 mm)
7
1-3/16 (30mm)
18-M4 HOLES
7xP.3-15/16 (100)=27-9/16 (700mm)
5-7/8 (150 mm)
13 (330mm)
(ALL AROUND)
5
3
30-11/16 (780mm)
3-15/16 (100 mm)
4
7/8 (23mm)
9
3-9/16 (90mm)
31-1/2 (800mm)
3-1/8 (80mm)
3-15/16 (100mm)
3-15/16 (100mm)
32-5/16 (820mm)
3-1/8 (80mm)
6-11/16 (170mm)
<IN CASE OF BACK-SUCTION>
20-M5 HOLES
PROTECTION NET10
(ALL AROUND)
AIR FILTER (ACCESSORY)
9
SUSPENSION BRACKET
8
3-15/16 (100mm)
POWER SUPPLY CONNECTION
7
INFRARED RECEIVER UNIT CONNECTION
6
1. IN CASE OF BACK-SUCTION,
NOTE)
10
CONTROL BOX5
MOUNT CHAMBER COVER TO BOTTOM SIDE OF THE UNIT.
IN CASE OF BOTTOM-SUCTION,
6-5/16 (160mm)
I.D.φ 31/32 (φ 25mm) (OUTLET)
DRAIN HOSE (ACCESSORY)
4
7-7/8 (200mm)
7-1/16 (180mm)
6
MOUNT CHAMBER COVER TO BACK SIDE OF THE UNIT.
SOCKET FOR DRAIN
VP20 O.D.φ 1-1/32 (φ 26mm)
3
2. LOCATION OF UNIT'S NAME PLATE: CONTROL BOX COVER
5-1/8 (130mm)
7xP.3-15/16 (100mm)=27-9/16 (700mm)
3. MOUNT THE AIR FILTER AT THE SUCTION SIDE.
/I.D.φ 25/32 (φ 20mm)
)(
SELECT ITS COLORIMETHOD (GRAVITY METHOD)
30-11/16 (780mm)
3-15/16 (100mm)
)
(
50% OR MORE.
GAS PIPE CONNECTION
φ 1/2 (φ 12.7mm) (FLARE CONNECTION)
2
31-1/2 (800mm)
3-9/16 (90mm)
9
3/8 (10mm)
IT CAN NOT BE EQUIPPED WITH AIR FILTER (ACCESSORY)
32-5/16 (820mm)
3-1/8 (80mm)
13/16 (20mm)
LIQUID PIPE CONNECTION
1
φ 1/4 (φ 6.4mm) (FLARE CONNECTION)
WHEN CONNECTING DUCT TO SUCTION SIDE.
1-15/16 (50mm)
< IN CASE OF BOTTOM-SUCTION >
NAME
DESCRIPTION
NUMBER
(IN CASE OF
BOTTOM SUCTION)
3D075268
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 15 16

Comments to this Manuals

No comments