INSTALLATION MANUAL
SPLIT SYSTEM Air Conditioners
English
Français
Español
MODELS
Ceiling-mounted Cassette type (Multi fl ow model)
FCQ18PVJU
FCQ24PVJU
FCQ30PVJU
Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
This manual should be left with the equipment owner.
Lire soigneusement ces instructions avant l’installation.
Conserver ce manuel à portée de main pour référence ultérieure.
Ce manuel doit être donné au propriétaire de l’équipement.
Lea cuidadosamente estas instrucciones antes de instalar.
Guarde este manual en un lugar a mano para leer en caso de tener alguna duda.
Este manual debe permanecer con el propietario del equipo.
00_CV_3PN06240-13M.indd 100_CV_3PN06240-13M.indd 1 12/18/2008 8:35:26 PM12/18/2008 8:35:26 PM
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - INSTALLATION MANUAL

INSTALLATION MANUALSPLIT SYSTEM Air ConditionersEnglishFrançaisEspañolMODELSCeiling-mounted Cassette type (Multi fl ow model)FCQ18PVJUFCQ24PVJUFCQ30PVJ

Page 2 - SAFETY CONSIDERATIONS1

9 English NOTEThe incline of attached drain hose (1) should be 2 15/16 in. • or less so that the drain socket does not have to stand additional force

Page 3 - BEFORE INSTALLATION2

English 10SPECIFICATIONS FOR FIELD SUPPLIED 9-3 FUSES AND WIRESModelPower supply wiring Transmission wiringField fuses Size Wire SizeFCQ18PVJUFCQ24PV

Page 4

11 EnglishConnect wires of the same gauge to both sides.Tightening torque for the terminal screws.2. Use the correct screwdriver for tightening the t

Page 5

English 12Turn the MAIN/SUB changeover switch on one of the two (2) remote controllers PC boards to “S”.(Leave the switch of the other remote control

Page 6 - INSTALLATION PROCEDURES FOR

13 EnglishTEST OPERATION13. Refer to the section of “FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS F

Page 7 - INDOOR UNIT INSTALLATION6

English 14E5 Compressor motor lock malfunctionE7Outdoor fan motor lock malfunctionOutdoor fan instantaneous overcurrent malfunctionE9 Electronic expa

Page 8 - REFRIGERANT PIPING WORK7

3PN06240-13M EM08A095 (0902)HT00_CV_3PN06240-13M.indd 200_CV_3PN06240-13M.indd 2 12/18/2008 8:35:26 PM12/18/2008 8:35:26 PM

Page 9 - DRAIN PIPING WORK8

SPLIT SYSTEM Air Conditioners Installation manual1 EnglishCONTENTS1. SAFETY CONSIDERATIONS ... 12. BEFORE INS

Page 10 - ELECTRIC WIRING WORK9

English 2When wiring the power supply and connecting the •remote controller wire and transmission wire, position the wires so that the control box l

Page 11 - THE REMOTE CONTROLLER

3 EnglishThis unit, both indoor and outdoor, is suitable for installation • in a commercial and light industrial environment.If installed as a househ

Page 12 - WIRING EXAMPLE10-2

English 4Where condensate can be properly drained.• Where the false ceiling is not noticeably on an incline.• Where suffi cient clearance for maintena

Page 13 - FIELD SETTING11

5 English(Opening dimension inside the frame for ceiling)33 13/16FrameFalse ceiling13/16 or more 33 13/16-*35 13/1613/16 or more(Ceiling-panel overla

Page 14 - TEST OPERATION13

English 6Insulation(field supply)Put the insulation tightly around the hole of the unit as shown. The ends of the side plate and the inner insulation

Page 15 - English 14

7 EnglishREFRIGERANT PIPING WORK7. GENERAL INSTRUCTIONS7-1 For refrigerant pipe of outdoor units, see the installation • manual attached to the outdo

Page 16 - EM08A095

English 8 CAUTIONBe sure to insulate any fi eld piping all the way to the piping • connection inside the unit. Any exposed pipe may cause condensate o