Daikin WMC Specifications Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
The filters are current-rated devices. In order to properly size a filter, it is necessary to know the operating
voltage and the input current rating of the drive. No derating or re-rating is necessary when applying the filter at
voltages that are less than or equal to the maximum voltage listed on the filter.
The IEEE 519-1991 Standard
The Institute of Electrical and Electronics Engineers (IEEE) has developed a standard that defines acceptable
limits of system current and voltage distortion. A simple form is available from McQuay that allows McQuay to
determine compliance with IEEE 519-1991.
Line reactors, isolation transformers, or phase-shifting transformers can be required on some installations.
Figure 16, Typical WMC Power Wiring
GND
L1
L2
L3
AC Input
Voltage
Manual
Disconnect
Optional
Contactor
Optional
EMI
Filter
Standard
Line
Reactor
(2) Hamonic
Filter with
Circuit Breaker
Notes:
(1) Single hole, crimp type compression terminal required.
(2) Connect to filter circuit breaker lugs.
(3) Conductors to be sized for 125 minimum circuit ampacity.
Size 1 AWG, 75°C wire recommended.
C
(1)
WMC Wiring
(3)
Page view 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 45 46