Installation and Maintenance Manual
IMM AGZ-7
Group: Chiller
Part Number: 331374001
Effective: February 2005
Supercedes: IOMM AGZ-6
Air-Cooled Scroll Compressor Chiller
AGZ 026BS/BH through 130BS/BH, Packaged
AGZ 026BB/BM through 130BB/BM, Remote Evaporator
60 Hertz, R-22, R-407c
Page view 0
1 2 3 4 5 6 ... 71 72

Summary of Contents

Page 1 - 60 Hertz, R-22, R-407c

Installation and Maintenance Manual IMM AGZ-7 Group: Chiller Part Number: 331374001 Effective: February 2005 Supercedes: IOMM AGZ-6 Air-Coo

Page 2 - Table of Contents

10 AGZ 026B through 130B IMM AGZ-7 Case 4, Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or

Page 3 - Introduction

IMM AGZ-7 AGZ 026B through 130B 11 Case 5, Pit/Solid Wall Installation Pit installations can cause operating problems and great care should be exerc

Page 4 - Installation

12 AGZ 026B through 130B IMM AGZ-7 Spring Isolator Dimensions Neoprene-in-Shear Dimensions Color Code L W H B C D Gray 5.5 3.37 1.75 0.5 4.12

Page 5 - Location

IMM AGZ-7 AGZ 026B through 130B 13 Table 2, AGZ-BS/BH, Isolator Loads At Each Mounting Location (With Aluminum Fins) 1 2 3 4 5 6 Total Unit (1) C

Page 6 - General

14 AGZ 026B through 130B IMM AGZ-7 Table 5, AGZ BM/BB, Isolator Loads At Each Mounting Location (With Aluminum Fins) AGZ-BM/BB Model Shipping Wt Op

Page 7

IMM AGZ-7 AGZ 026B through 130B 15 Table 8,AGZ BM/BB, Isolator Locations ACZ-BS, AGZ-BM Less Evaporator Units Operating Weight Neoprene-In-Shear Mo

Page 8

16 AGZ 026B through 130B IMM AGZ-7 Winter Operation Temperatures 0°F to 34°F 35°F and Above Fan Control Optional VFD (1) Standard FanTrol (2

Page 9 - Chiller 1 Chiller 2 Chiller 3

IMM AGZ-7 AGZ 026B through 130B 17 These minimum flow rates assume that flow will be reduced proportionally to the cooling load. Table 9, Minimum Pa

Page 10 - Case 4, Open Screening Walls

18 AGZ 026B through 130B IMM AGZ-7 CAUTION If separate disconnect is used for the 115V supply to the evaporator heating cable, mark the disconnect

Page 11

IMM AGZ-7 AGZ 026B through 130B 19 Figure 17, AGZ 026 - AGZ 070, Typical Field Evaporator Water Piping AirVentFlowSwitchVibrationEliminatorsDrainOut

Page 12 - Vibration Isolators

2 AGZ 026B through 130B IMM AGZ-7 Table of Contents Introduction... 3 General Description...

Page 13 - Table 4, Isolator Locations

20 AGZ 026B through 130B IMM AGZ-7 Water Connections Bring water piping to the evaporator through the side between the vertical supports. Provide t

Page 14 - Aluminum Fins)

IMM AGZ-7 AGZ 026B through 130B 21 Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service stations) to det

Page 15 - Standard/High Ambient Panels

22 AGZ 026B through 130B IMM AGZ-7 Altitude Correction Factors Performance tables are based at sea level. Elevations other than sea level affect the

Page 16 - Panel Ratings

IMM AGZ-7 AGZ 026B through 130B 23 Table 16, Capacity and Power Derates, Models AGZ 075B to 130B Fouling Factor Chilled Water Delta T 0.0001 (0.017

Page 17 - Water Piping

24 AGZ 026B through 130B IMM AGZ-7 Operating/Standby Limits Maximum standby ambient air temperature, 130°F (55°C) Maximum operating ambient air temp

Page 18 - THERMOWELL

IMM AGZ-7 AGZ 026B through 130B 25 Figure 19, AGZ 026B – 130B, Evaporator Pressure Drop 026-030075-085-090100-110120-130035040045050055065-070060 Mi

Page 19 - Flow Switch

26 AGZ 026B through 130B IMM AGZ-7 Wind Baffles and Hail Guards Protection against negative effects from wind and protection against fin damage fro

Page 20 - Glycol Solutions

IMM AGZ-7 AGZ 026B through 130B 27 Table 17, Packing List Description Part Number Bubble Number Vertical Support Rib 074758501 1 Top Cover 330409

Page 21

28 AGZ 026B through 130B IMM AGZ-7 Optional Features Controls Hot Gas Bypass Hot gas bypass permits unit operation down to 10% of full load capacity

Page 22 - Fouling Factor

IMM AGZ-7 AGZ 026B through 130B 29 These documents can also be found on www.mcquay.com under Product Information > (chiller type) > Control In

Page 23 - Evaporator Freeze Protection

IMM AGZ-7 AGZ 026B through 130B 3 Introduction General Description McQuay Air-Cooled Global Water Chillers are complete, self-contained automatic re

Page 24 - Limitations

30 AGZ 026B through 130B IMM AGZ-7 Electrical Multi-Point Electrical Connection Provides a power connection to each of the unit’s two electrical ci

Page 25

IMM AGZ-7 AGZ 026B through 130B 31 Physical Data AGZ-BS/BH Table 19, AGZ 026BS/BH through 035BS/BH AGZ MODEL NUMBER PHYSICAL DATA 026B 030B 035B BAS

Page 26 - Top Panel Attachment (Last)

32 AGZ 026B through 130B IMM AGZ-7 Table 20, AGZ 040BS/BH through 055BS/BH AGZ MODEL NUMBER PHYSICAL DATA 040B 045B 050B 055B BASIC DATA Ckt.1 Ckt

Page 27 - Front Panel 330409501 3

IMM AGZ-7 AGZ 026B through 130B 33 Table 21, AGZ 060BS/BH through 070BS/BH AGZ MODEL NUMBER PHYSICAL DATA 060B 065B 070B BASIC DATA Ckt.1 Ckt.2 C

Page 28 - Optional Features

34 AGZ 026B through 130B IMM AGZ-7 Table 22, AGZ 075BS/BH through 090BS/BH AGZ MODEL NUMBER PHYSICAL DATA 075B 085B 090B BASIC DATA Ckt.1 Ckt.2 Ckt

Page 29

IMM AGZ-7 AGZ 026B through 130B 35 Table 5, AGZ 100BS/BH through 130BS/BH AGZ MODEL NUMBER PHYSICAL DATA 100B 110B 120B 130B BASIC DATA Ckt.1 Ckt.2

Page 30 - Electrical

36 AGZ 026B through 130B IMM AGZ-7 Electrical Data, Standard Ambient Table 23, AGZ 026BM/BS – 070BM/BS, Electrical Data, Single Point (105°F and be

Page 31 - Physical Data

IMM AGZ-7 AGZ 026B through 130B 37 Table 24, AGZ 026BM/BS – 070BM/BS, Compressor and Fan Motor Amps, Single and Multi-Point (105°F and below)) Rated

Page 32

38 AGZ 026B through 130B IMM AGZ-7 Table 25, AGZ 026 BM/BS – 070BM/BS, Field Wiring, Single Point (105°F and below) Wiring to Standard Power Block

Page 33

IMM AGZ-7 AGZ 026B through 130B 39 Table 26, AGZ 075BM/BS – 130BM/BS, Electrical Wiring, Single Point (105°F and below) Power Supply Max. Fuse Fi

Page 34

4 AGZ 026B through 130B IMM AGZ-7 Installation Note: Installation is to be performed by qualified personnel who are familiar with local codes and re

Page 35

40 AGZ 026B through 130B IMM AGZ-7 Table 27, AGZ 075BM/BS – 130BM/BS, Compressor and Fan Motor Amps, Single and Multi-Point (105°F and below) Rated

Page 36 - (105°F and below)

IMM AGZ-7 AGZ 026B through 130B 41 Table 28, AGZ 075BM/BS - 130BM/BS, Field Wiring, Single Point (105°F and below) Wiring to Standard Power Block W

Page 37

42 AGZ 026B through 130B IMM AGZ-7 Table 29, AGZ 026BM/BS – 070BM/BS, Electrical Data, Multi-Point (105°F and below) Electrical Circuit #1 Electri

Page 38

IMM AGZ-7 AGZ 026B through 130B 43 Table 30, AGZ 026BM/BS - 070BM/BS, Field Wiring, Multi-Point (105°F and below) Wiring to Standard Power Block W

Page 39

44 AGZ 026B through 130B IMM AGZ-7 Table 31, AGZ 075BM/BS - 130BM/BS, Field Wiring Data (105°F and below) Wiring to Standard Power Block Wiring to

Page 40

IMM AGZ-7 AGZ 026B through 130B 45 Table 32, AGZ 065BM/BS - 130BM/BS, Electrical Data, Multi-Point (105°F and below) Electrical Circuit #1 Electri

Page 41

46 AGZ 026B through 130B IMM AGZ-7 Electrical Data High Ambient Table 33, AGZ 026BB/BH – 070BB/BH, Electrical Data, Single Point (Above 105°F to 12

Page 42

IMM AGZ-7 AGZ 026B through 130B 47 Table 34, AGZ 026BB/BH – 070BB/BH, Compressor and Fan Motor Amps, Single and Multi-Point (Above 105°F to 125°F))

Page 43

48 AGZ 026B through 130B IMM AGZ-7 Table 35, AGZ 026BB/BH - 070BB/BH, Electrical Data, Multi-Point (Above 105°F to 125°F) Electrical Circuit #1 El

Page 44

IMM AGZ-7 AGZ 026B through 130B 49 Table 36, AGZ 075BB/BH – 130BB/BH, Electrical Data, Single Point (Above 105°F to 125°F) Power Supply Max. Fuse

Page 45

IMM AGZ-7 AGZ 026B through 130B 5 Location Unit Placement AGZ units are for outdoor applications and can be mounted either on a roof or at ground le

Page 46 - Electrical Data High Ambient

50 AGZ 026B through 130B IMM AGZ-7 Table 37, AGZ 075BB/BH – 130BB/BH, Compressor and Fan Motor Amps, Single and Multi-Point (Above 105°F to 125°F) R

Page 47 - F to 125

IMM AGZ-7 AGZ 026B through 130B 51 Table 38, AGZ 075BB/BH – 130BB/BH, Electrical Data, Multi-Point (Above 105°F to 125°F) Electrical Circuit #1 E

Page 48

52 AGZ 026B through 130B IMM AGZ-7 Notes for “Electrical Data Single- and Multi-Point” Power: 1. Unit wire size ampacity (MCA) is equal to 125% of

Page 49 - (Above 105

IMM AGZ-7 AGZ 026B through 130B 53 Figure 22, AGZ 026B – AGZ 130B, Typical Field Wiring DWG. 330423101 REV.0ATB2IF REMOTE STOPCONTROL IS USED,REMOV

Page 50

54 AGZ 026B through 130B IMM AGZ-7 Dimensional Data Figure 23, Dimensions, AGZ 026BS – 070BS Packaged Chiller 67.76 (1721.10)13.31(338.07)13.31(338

Page 51

IMM AGZ-7 AGZ 026B through 130B 55 Figure 24, AGZ 075BS - 090BS Packaged Chiller YZ15.5(392)28.5 (724)28.5(724)134.9 (3426)X100.4(2550)14.4(364)6.4

Page 52 - Voltage Limitations:

56 AGZ 026B through 130B IMM AGZ-7 Figure 25, AGZ 100BS - 130BS Packaged Chiller "B""C"33.7(855)25.2(641)67.8 (1721)12.4 (315)2

Page 53 - RATED 600 VOLTS

IMM AGZ-7 AGZ 026B through 130B 57 R-407C Units AGZ chillers are available with R-407C refrigerant as non-ARI certified units. R-407C is a zeotropi

Page 54

58 AGZ 026B through 130B IMM AGZ-7 Start the system and observe operation. Use standard charging procedures (liquid only) to top off the charge. It

Page 55

IMM AGZ-7 AGZ 026B through 130B 59 Startup Pre Start-up The chiller must be inspected to ensure no components became loose or damaged during shippi

Page 56 - POWER ENTRY POINT

6 AGZ 026B through 130B IMM AGZ-7 Restricted Air Flow General The clearances required for design-life operation of AGZ air-cooled condensers are des

Page 57 - R-407C Units

60 AGZ 026B through 130B IMM AGZ-7 Shutdown Temporary 1. Put both circuit switches to the OFF position (Pumpdown and Stop). 2. After compressors h

Page 58

IMM AGZ-7 AGZ 026B through 130B 61 Electrical Check Out CAUTION Electrical power must be applied to the compressor crankcase heaters 24 hours befo

Page 59 - Startup

62 AGZ 026B through 130B IMM AGZ-7 The bypass valve includes a solenoid valve that is controlled by the MicroTech II controller. It is active when

Page 60 - Refrigerant Piping Checkout

IMM AGZ-7 AGZ 026B through 130B 63 Thermostatic Expansion Valve The expansion valve performs one specific function. It keeps the evaporator supplie

Page 61 - Component Operation

64 AGZ 026B through 130B IMM AGZ-7 Unit Maintenance General On initial start-up and periodically during operation, it will be necessary to perform c

Page 62 - Refrigerant Charging

IMM AGZ-7 AGZ 026B through 130B 65 Liquid Line Sight Glass The refrigerant sight glasses should be observed periodically. (A weekly observation sho

Page 63 - Evaporator

66 AGZ 026B through 130B IMM AGZ-7 Service WARNING Service on this equipment is to be performed by qualified refrigeration personnel familiar with

Page 64 - Unit Maintenance

IMM AGZ-7 AGZ 026B through 130B 67 Evaporator The evaporators are the direct expansion, shell-and-tube type with refrigerant flowing through the tub

Page 65

68 AGZ 026B through 130B IMM AGZ-7 Procedure to charge a moderately undercharged AGZ unit: 1. If a unit is low on refrigerant, you must first deter

Page 66 - Service

IMM AGZ-7 AGZ 026B through 130B 69 AGZ Troubleshooting Chart PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS 1. Main switch. 1. Close switch. 2

Page 67

IMM AGZ-7 AGZ 026B through 130B 7 Case 1, Building or Wall on One Side of One Unit The existence of a screening wall or the wall of a building in cl

Page 68 - Warranty Statement

70 AGZ 026B through 130B IMM AGZ-7 PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS 1. Oil hang-up in piping 1. Review refrigerant piping and

Page 70

Post Office 2510, Staunton, Virginia 24402 USA • (800) 432-1342 • www.mcquay.com IMM AGZ-7 (2/05) This document contains the mos

Page 71

8 AGZ 026B through 130B IMM AGZ-7 Case 2, Two Units Side By Side Two or more units sited side by side are common. If spaced closer than 12 feet (3.

Page 72

IMM AGZ-7 AGZ 026B through 130B 9 Case 3, Three or More Units Side By Side When three or more units are side by side, the outside chillers (1 and 3