Daikin RXYQ26PY1 Installation Manual

Browse online or download Installation Manual for Heat pumps Daikin RXYQ26PY1. Daikin RXYQ26PY1 Installation manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
INSTALLATION MANUAL
Installation manual
VRVW
III
System air conditioner
Installationsanweisung
VRVW
III
System Klimaanlage
Manuel d’installation
Conditionneur d’air VRVW
III
System
Manual de instalación
Acondicionador de aire con sistema VRVW
III
Manuale di installazione
Condizionatore d’aria a sistema VRVW
III
Εγχειρßδιο εγκατÜστασηò
Κλιìατιστικü ìε σýστηìα VRVW
III
Installatiehandleiding
Airconditioner met VRVW
III
Systeem
Manual de instalação
Ar condicionado VRVW
III
System
Рóêоводство по монтажó
Кондиционер системы VRVW
III
English
Deutsch
Français
Español
Italiano
Nederlands
Portugues
System air conditioner
RWEYQ8PY1
RWEYQ10PY1*
RWEYQ16PY1
RWEYQ18PY1
RWEYQ20PY1*
RWEYQ24PY1
RWEYQ26PY1
RWEYQ28PY1
RWEYQ30PY1*
*Only models with suffix numbers
10, 20, and 30 are sold in China.
00_CV_3P153897-8L.fm Page 1 Friday, July 11, 2008 4:45 PM
Page view 0
1 2 3 4 5 6 ... 21 22

Summary of Contents

Page 1 - INSTALLATION MANUAL

INSTALLATION MANUALInstallation manualVRVWIII System air conditionerInstallationsanweisungVRVWIII System KlimaanlageManuel d’installationConditionneur

Page 2 - Machinery Safety 98/37/EC

5 English5.Carry out complete cooling/thermal insulation of water piping and outdoor dehumidification. If complete cooling or thermal insula-tion has

Page 3 - ABCF1 F1F2 F2 Q1 Q2

English 62.Because the plate type heat exchanger has a structure which does not permit disassembling and cleaning, follow the following procedures for

Page 4 - F1 F2 F1 F2

7 English8-4 ExamplesSystem example (Refer to figure 8)1. Field power supply2. Main switch3. Earth leak detector4. Fuse5. Cool/heat selector6. Remote

Page 5

English 8• The wiring to the indoor units must be connected to the F1/F2 (To IN/D UNIT) terminals on the PC board in the outside unit.Field line conne

Page 6 - 1. SAFETY PRECAUTIONS

9 English9. REFRIGERANT PIPINGCautionAfter completing installation, be sure to open the valve. (See 9-9 Additional refrigerant charge for details) (Op

Page 7 - 2. INTRODUCTION

English 10Not recommendable but in case of emergencyYou must use a torque wrench but if you are obliged to install the unit without a torque wrench, y

Page 8 - 3. SELECTION OF LOCATION

11 English9-5 Example of connection∗ Below table is mentioned about the case of heat recovery sytem (3-piping: suction gas, HP/LP gas and liquid pipes

Page 9 - English 4

English 12Required Conditions Example Drawings1. It is necessary to increase the liquid and suction gas pipe size between the first branch kit and the

Page 10 - 5 English

13 English9-6 Air tight test and vacuum dryingThe units were checked for leaks by the manufacturer.Confirm that the valves are firmly closed before Ai

Page 11 - 8. FIELD WIRING

English 14Additional refrigerant charge procedure (2)-by Additional refrig-erant charge operationAbout the system settings for additional refrigerant

Page 12 - 7 English

Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-Ku, Osaka, 530-8323 JapanDAIKIN INDUSTRIES, LTD.EN60335-2-40,3P216950-1CNoboru MurataManager Quality C

Page 13 - English 8

15 English(Refer to figure 27)1. Electrical box2. Cover of electrical box3. Cover for servicing4. Inspection cover5. Points to be noted when providing

Page 14 - 9. REFRIGERANT PIPING

English 1612. CAUTION FOR REFRIGERANT LEAKS(Points to note in connection with refrigerant leaks)IntroductionThe installer and system specialist shall

Page 15 - English 10

3P153897-8L EM08A055(0808) HT00_CV_3P153897-8L.fm Page 5 Friday, July 11, 2008 4:45 PM

Page 16 - 11 English

12figure 1figure 4[1]234744400808012456712891110313figure 10figure 51289345671011figure 8123A B CA B C F1 F1F2 F2 Q1 Q2F1 F2 F1 F2 F1 F2F1 F2

Page 17 - English 12

1234567OUT-OUT OUT-OUT OUT-OUTF1 F2F1 F2F1 F2 F1 F2LOW NOISEfigure 13figure 15124365891071211131415A B CA B C1DS11234OFFONOUTI NTO IN/DUNITF1 F2A1

Page 18 - 13 English

111122434355R410AR410A9778139661610 1010 101712121415151818[Heat pump system][Heat recovery system]figure 2445321figure 25 figure 261122334456[Heat re

Page 19 - 11. TEST RUN

1 EnglishRWEYQ8PY1RWEYQ10PY1RWEYQ16PY1RWEYQ18PY1RWEYQ20PY1RWEYQ24PY1RWEYQ26PY1RWEYQ28PY1RWEYQ30PY1VRVWIII System air conditioner Installation manualCO

Page 20 - 15 English

English 2• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel

Page 21 - English 16

3 English2-2 Standard operation limitThe figures below assume following operating conditions for indoor and outside units:Equivalent pipe length ...

Page 22 - 3P153897-8L EM08A055

English 43. Remote controller4. Cool/heat selector5. Personal computer or radioIf the electric wave of AM broadcasting is particularly weak, keep dist

Comments to this Manuals

No comments